Programming
700 Relay 3, function (RELAY3 FUNCTION)
703 Relay 4, function (RELAY4 FUNCTION)
706 Relay 5, function (RELAY5 FUNCTION)
709 Relay 6, function (RELAY6 FUNCTION)
Function:
This output activates a relay switch.
Relay outputs 3/4/5/6 can be used for showing
status and warnings. The relay is activated when the
conditions for the relevant data values have been
fulfilled.
Activation/deactivation can be programmed in
parameters 701/704/707/710
Relay 3/4/5/6, ON
delay
and parameters 702/705/708/711
Relay 3/4/5/
6, OFF delay
.
See technical data on page 73.
Description of choice:
See data choice and connections on page 106.
701 Relay 3, ON delay (RELAY3 ON DELAY)
704 Relay 4, ON delay (RELAY4 ON DELAY)
707 Relay 5, ON delay (RELAY5 ON DELAY)
710 Relay 6, ON delay (RELAY6 ON DELAY)
Value:
0 - 600 sec.
★
0 sec.
Function:
This parameter allows a delay of the cut-in time of
relays 3/4/5/6 (terminals 1-2).
Description of choice:
Enter the required value.
702 Relay 3, OFF delay (RELAY3 OFF DELAY)
705 Relay 4, OFF delay (RELAY4 OFF DELAY)
708 Relay 5, OFF delay (RELAY5 OFF DELAY)
711 Relay 6, OFF delay (RELAY6 OFF DELAY)
Value:
0 - 600 sec.
★
0 sec.
Function:
This parameter is used to delay the cut-out time of
relays 3/4/5/6 (terminals 1-2).
Description of choice:
Enter the required value.
NB!
Parameters 700-711 for relay cards are only
activated if a relay option card is fitted to the
VLT 6000 HVAC.
Ordering numbers can be seen from the Design
Guide.
Relay 6-9:
A-B break, A-C make
Max. 240 V AC, 2 Amp.