VLT
®
6000 HVAC
74
MG.60.B1.02 - VLT is a registered Danfoss trade mark
Quick menu: Parameter 1 of 12
Used to select the language for the display.
Quick menu: Parameter 2 of 12
Select the kW value that equals the rated motor value
P
M,N
. There is a choice of four undersizes or one oversize
in relation to the factory setting.
Quick menu: Parameter 3 of 12
Used to set the rated motor voltage U
M,N
while taking into
consideration whether the motor is star or delta
connected.
Quick menu: Parameter 4 of 12
Used to select the rated motor frequency f
M,N
.
Quick menu: Parameter 5 of 12
Used to select motor current I
M,N
while taking into
consideration whether the motor is star or delta
connected.
Quick menu: Parameter 6 of 12
Used to select the value that corresponds to the rated
motor speed n
M,N
that can be seen from the nameplate
data.
Quick menu: Parameter 7 of 12
Used to select a minimum frequency limit,
corresponding to the lowest frequency at which the
motor is to run.
Quick menu: Parameter 8 of 12
Used to select a maximum frequency limit,
corresponding to the highest frequency at which the
motor is to run.
Quick menu: Parameter 9 of 12
The ramp-up time is the acceleration time from 0 Hz to
the rated motor frequency f
M,N
(parameter 104).
Quick menu: Parameter 10 of 12
The ramp-down time is the deceleration time from the
rated motor frequency f
M,N
(parameter 104) to 0 Hz.
Quick menu: Parameter 11 of 12
Relay output 1 can be used for indicating status and
warnings. The relay is activated when the conditions for
the relevant data values have been fulfilled.
Quick menu: Parameter 12 of 12
Relay output 2 can be used for indicating status and
warnings. The relay is activated when the conditions for
the relevant data values have been fulfilled.
■
■
■
■
■
Quick menu
The [QUICK MENU] key gives access to the 12
most important parameters of the VLT frequency
converter. After programming, the VLT frequency
converter will in most cases be ready
for operation. Scroll through the
Quick menu using the [+/-]
keys and change the
data values by
pushing [CHANGE
DATA] + [OK].
4 of 12
MOTOR
FREQUENCY
par. 104
3 of 12
MOTOR VOLTAGE
par. 103
2 of 12
MOTOR POWER
par. 102
1 of 12
LANGUAGE
par. 001
5 of 12
MOTOR
CURRENT
par. 105
6 of 12
RATED MOTOR
SPEED
par. 106
7 of 12
OUTPUT FREQUENCY,
LOW LIMIT
par. 201
8 of 12
OUTPUT FREQUENCY,
HIGH LIMIT
par. 202
9 of 12
RAMP-UP TIME
par. 206
10 of 12
RAMP-DOWN
TIME
par. 207
11 of 12
RELAY 1 OUTPUT
par. 323
12 of 12
RELAY 2 OUPUT
par. 326
[+]
[+]
[+]
[+]
[+]
[+]
[+]
[+]
[+]
[+]
[+]
[+]
[-]
[-]
[-]
[-]
[-]
[-]
[-]
[-]
[-]
[-]
[-]
[-]
SETUP
1
USE +/- 40Hz
HAND LOCAL RUN
40Hz
0 -----
60