2.1.8 Initial Commissioning
The easiest way of carrying out the initial commissioning is by using the quick menu button and follow the quick set-up
procedure using LCP 102 (read table from left to right). The example applies to open-loop applications:
Press
Q2 Quick Menu
Set Language
Set Motor Nameplate Power
Set Nameplate Voltage
Set Nameplate Frequency
Set Nameplate Current
Set Nameplate speed in RPM
5-12 Terminal 27 Digital
Input
If terminal default is
Coast
inverse,
it is possible to change
this setting to
No function
. No
connection to terminal 27 is
then needed for running AMA
Set desired AMA function.
Enable complete AMA is
recommended
Set the minimum speed of the
motor shaft
Set the maximum speed of the
motor shaft
Set the ramping up time with
reference to synchronous motor
speed, n
s
Set the ramping downdecel
time with reference to
synchronous motor speed, n
s
Set the site from where the
reference must work
How to Program
FC 300 Programming Guide
MG.33.MA.22 - VLT
®
is a registered Danfoss trademark