14-53 Fan Monitor
Option:
Function:
Select which action the adjustable frequency drive
should take in case a fan fault is detected.
[0]
Disabled
[1]
*
Warning
[2]
Trip
14-55 Output Filter
Option:
Function:
Select the type of output filter connected. This
parameter cannot be adjusted while motor is
running.
[0]
*
No
Filter
This is the default setting and should be used with
dU/dt filters or high frequency common mode (HF-
CM) filters.
[1]
Sine-
Wave
Filter
This setting is only for backwards compatibility. It
enables operation with FLUX control principle when
the parameters 14-56 and 14-57 are programmed
with the output filter capacitance and inductance. It
DOES NOT limit the range of the switching
frequency.
[2]
Sine-
Wave
Filter
Fixed
This parameter sets a minimum allowed limit to the
switching frequency and ensures that the filter will
be operated within the safe range of switching
frequencies. Operation is possible with all control
principles. For FLUX control principle the
parameters 14-56 and 14-57 have to be
programmed (these parameters have no effect in
VVC+ and U/f). The modulation patter will be set to
SFAVM which gives the lowest acoustic noise in the
filter. Remember to set parameter 14-55 to Sine-
wave fixed always when you use a sine-wave filter.
14-56 Capacitance Output Filter
Compensation function of the LC filter requires the per phase
equivalent star connected capacitance of the filter (3 times the
capacity between two phases when capacitance is ’Delta’
connection).
Range:
Function:
Application
dependent
*
[0.1 - 6500.0
uF]
Set the capacitance of the
output filter. The value can
be found on the filter label.
NOTE!
This is required for
correct compensation in
flux mode (
14-57 Inductance Output Filter
Range:
Function:
Application
dependent
*
[0.001 -
65.000 mH]
Set the inductance of the output
filter. The value can be found on
the filter label.
NOTE!
This is required for correct
compensation in flux mode
(
)
3.15.7 14-7* Compatibility
The parameters in this group are for setting the compatibility
for VLT 3000, VLT 5000 to FC 300
14-72 VLT Alarm Word
Option:
Function:
[0] 0 - 4294967295 Read out the alarm word corresponding to
VLT 5000
14-73 VLT Warning Word
Option:
Function:
[0] 0 - 4294967295 Read out the warning word corresponding to
VLT 5000
14-74 VLT Ext. Status Word
Range:
Function:
0
*
[0 - 4294967295 ] Read out the ext. status word
corresponding to VLT 5000
3.15.8 14-8* Options
14-80 Option Supplied by External 24 V DC
Option:
Function:
[0]
No
Select No [0] to use the drive's 24 V DC supply.
[1]
*
Yes Select Yes [1] if an external 24 V DC supply will be used
to power the option. Inputs/outputs will be galvanically
isolated from the drive when operated from an external
supply.
NOTE!
This parameter is only changing function by performing a
power cycle.