No. Description
Warning
Alarm/Trip
Alarm/Trip Lock
Parameter
Reference
52
AMA low I
nom
X
53
AMA motor too big
X
54
AMA motor too small
X
55
AMA parameter out of range
X
56
AMA interrupted by user
X
57
AMA timeout
X
58
AMA internal fault
X
X
59
Current limit
X
60
External Interlock
X
X
61
Feedback Error
(X)
(X)
62
Output Frequency at Maximum Limit
X
63
Mechanical Brake Low
(X)
64
Voltage Limit
X
65
Control Board Overtemperature
X
X
X
66
Heatsink Temperature Low
X
67
Option Configuration has Changed
X
68
Safe Stop
(X)
(X)
1)
69
Pwr. Card Temp
X
X
70
Illegal FC configuration
X
73
Safe Stop Auto Restart
(X)
(X)
76
Power Unit Set-up
X
77
Reduced power mode
X
14-59 Actual Number of Inverter
Units
78
Tracking Error
(X)
(X)
79
Illegal PS config
X
X
80
Drive Initialized to default value
X
81
CSIV corrupt
X
82
CSIV param error
X
85
Profibus/Profisafe Error
X
90
Feedback Monitor
(X)
(X)
91
Analog input 54 wrong settings
X
S202
250 New spare part
X
14-23 Typecode Setting
251 New Type Code
X
X
Table 5.1 Alarm/Warning code list
(X) Dependent on parameter
1) Cannot be Auto reset via
14-20 Reset Mode
A trip is the action when an alarm has appeared. The trip will
coast the motor and can be reset by pressing the reset
button or make a reset by a digital input (par. group 5-1* [1]).
The original event that caused an alarm cannot damage the
adjustable frequency drive or cause dangerous conditions. A
trip lock is an action that occurs in conjunction with an
alarm, which may cause damage to the adjustable frequency
drive or connected parts. A trip lock situation can only be
reset by power cycling.
LED indication
Warning
yellow
Alarm
flashing red
Trip locked
yellow and red
Troubleshooting