5-20 Terminal X46/1 Digital Input
Option:
Function:
[0]
*
No operation This parameter is active when option module
MCB 113 is installed in the adjustable
frequency drive. Functions are described
under 5-1*
Digital Inputs
5-21 Terminal X46/3 Digital Input
Option:
Function:
[0]
*
No operation This parameter is active when option
moduleMCB 113 is installed in the adjustable
frequency drive. Functions are described
under 5-1*
Digital Inputs
5-22 Terminal X46/5 Digital Input
Option:
Function:
[0]
*
No operation This parameter is active when option
moduleMCB 113 is installed in the adjustable
frequency drive. Functions are described
under 5-1*
Digital Inputs
5-23 Terminal X46/7 Digital Input
Option:
Function:
[0]
*
No operation This parameter is active when option
moduleMCB 113 is installed in the adjustable
frequency drive. Functions are described
under 5-1*
Digital Inputs
5-24 Terminal X46/9 Digital Input
Option:
Function:
[0]
*
No operation This parameter is active when option module
MCB 113 is installed in the adjustable
frequency drive. Functions are described
under 5-1*
Digital Inputs
5-25 Terminal X46/11 Digital Input
Option:
Function:
[0]
*
No operation This parameter is active when option
moduleMCB 113 is installed in the adjustable
frequency drive. Functions are described
under 5-1*
Digital Inputs
5-26 Terminal X46/13 Digital Input
Option:
Function:
[0]
*
No operation This parameter is active when option module
MCB 113 is installed in the adjustable
frequency drive. Functions are described
under 5-1*
Digital Inputs
3.7.3 5-3* Digital Outputs
The 2 solid-state digital outputs are common for terminals 27
and 29. Set the I/O function for terminal 27 in
, and set the I/O function for terminal 29 in
. These parameters cannot be adjusted
while the motor is running.
[0]
No operation
Default for all digital outputs and relay
outputs
[1]
Control ready
The control card is ready. For example,
Feedback from a drive where the control
is supplied by an external 24 V (MCB 107)
and the main power to drive is not
detected.
[2]
Drive ready
The adjustable frequency drive is ready
for operation and applies a supply signal
on the control board.
[3]
Drive ready /
remote control
The adjustable frequency drive is ready
for operation and is in Auto On mode.
[4]
Enable / no
warning
Ready for operation. No start or stop
command is been given (start/disable).
No warnings are active.
[5]
VLT running
Motor is running and shaft torque is
present.
[6]
Running / no
warning
Output speed is higher than the speed
1-81 Min Speed for Function at Stop
. The motor is running and there are
no warnings.
[7]
Run in range/no
warning
Motor is running within the programmed
current and speed ranges set in
to
. There are no warnings.
[8]
Run on
reference / no
warning
Motor runs at reference speed. No
warnings.
[9]
Alarm
An alarm activates the output. There are
no warnings.
[10]
Alarm or warning An alarm or a warning activates the
output.
[11]
At torque limit
The torque limit set in
or
has been exceeded.
[12]
Out of current
range
The motor current is outside the range
set in
.
[13]
Below current,
low
Motor current is lower than set in
.
[14]
Above current,
high
Motor current is higher than set in
.
[15]
Out of speed
range
Output frequency is outside the
[16]
Below speed, low Output speed is lower than the setting in
Parameter Descriptions
FC 300 Programming Guide
MG.33.MA.22 - VLT
®
is a registered Danfoss trademark
3-53
3
3