NOTE!
Max. output frequency cannot exceed 10% of the inverter
switching frequency (
14-01 Switching Frequency
).
4-16 Torque Limit Motor Mode
Range:
Function:
Application
dependent
*
[Application
dependant]
This function limits the
torque on the shaft to
protect the mechanical
installation.
NOTE!
Changing
is set to
Speed open-loop
[0],
is automatically readjusted.
NOTE!
The torque limit reacts on the actual, non-filtrated torque,
including torque spikes. This is not the torque that is seen
from the LCP or the serial communication bus as that is
filtered.
4-17 Torque Limit Generator Mode
Range:
Function:
100.0 %
*
[Application
dependant]
This function limits the torque on
the shaft to protect the
mechanical installation.
NOTE!
The torque limit reacts on the actual, non-filtrated torque,
including torque spikes. This is not the torque that is seen
from the LCP or the serial communication bus as that is
filtered.
4-18 Current Limit
Range:
Function:
Application
dependent
*
[Application
dependant]
This is a true current limit function
that continues in the oversyn-
chronous range; however, due to
field weakening, the motor torque
at current limit will drop
accordingly when the voltage
increase stops above the
synchronized speed of the motor.
4-19 Max Output Frequency
Range:
Function:
132.0 Hz
*
[1.0 -
1000.0 Hz]
Provides a final limit on the output
frequency for improved safety in
applications where you want to avoid
accidental overspeeding. This limit is final
in all configurations (independent of the
setting in
NOTE!
Max. output frequency cannot exceed 10% of the inverter
switching frequency (
).
cannot be adjusted while the
motor is running.
4-20 Torque Limit Factor Source
Option:
Function:
Select an analog input for scaling the
settings in
and
from 0% to 100% (or inverse).
The signal levels corresponding to 0%
and 100% are defined in the analog
input scaling, e.g., par. group 6-1*. This
parameter is only active when
is in
Speed
Open-loop
or
Speed Closed-loop
.
[0]
*
No function
[2]
Analog in 53
[4]
Analog in 53 inv
[6]
Analog in 54
[8]
Analog in 54 inv
[10]
Analog in X30-11
[12]
Analog in X30-11 inv
[14]
Analog in X30-12
[16]
Analog in X30-12 inv
Parameter Descriptions
FC 300 Programming Guide
MG.33.MA.22 - VLT
®
is a registered Danfoss trademark
3-43
3
3