3.10 Parameters: 8-** Comm. and Options
3.10.1 8-0* General Settings
8-01 Control Site
Option:
Function:
The setting in this parameter overrides the
[0]
*
Digital and ctrl.
word
Control by using both digital input and
control word.
[1]
Digital only
Control by using digital inputs only.
[2]
Control word
only
Control by using control word only.
8-02 Control Word Source
Select the source of the control word: one of two serial interfaces or
four installed options. During initial power-up, the adjustable
frequency drive automatically sets this parameter to
Option A
[3] if
it detects a valid serial communication option installed in slot A. If
the option is removed, the adjustable frequency drive detects a
change in the configuration, sets
back to
default setting
FC
RS-485, and the adjustable frequency drive then
trips. If an option is installed after initial power-up, the setting of
will not change but the adjustable
frequency drive will trip and display: Alarm 67
Option Changed
.
When you retrofit a Bus option into a drive that did not have a Bus
option installed to begin with, you must take an ACTIVE decision to
move the control to Bus-based. This is done for safety reasons in
order to avoid an accidental change.
This parameter cannot be adjusted while the motor is running.
Option:
Function:
[0]
None
[1]
FC RS-485
[2]
FC USB
[3]
*
Option A
[4]
Option B
[5]
Option C0
[6]
Option C1
[30]
External Can
8-03 Control Word Timeout Time
Range:
Function:
1.0 s
*
[Application
dependant]
Enter the maximum time expected to pass
between the reception of two consecutive
messages. If this time is exceeded, it
indicates that the serial communication
has stopped. The function selected in
8-04 Control Word Timeout Function
will
then be carried out. The timeout counter
is triggered by a valid control word.
8-04 Control Word Timeout Function
Select the timeout function. The timeout function activates when
the control word fails to be updated within the time period
8-03 Control Word Timeout Time
.
Option:
Function:
[0]
*
Off
Resumes control via serial bus (serial
communication bus or standard) using the
most recent control word.
[1]
Freeze output Freezes output frequency until communi-
cation resumes.
[2]
Stop
Stops with auto-restart when communication
resumes.
[3]
Jogging
Runs the motor at JOG frequency until
communication resumes.
[4]
Max. speed
Runs the motor at maximum frequency until
communication resumes.
[5]
Stop and trip
Stops the motor, then resets the adjustable
frequency drive in order to restart: via the
serial communication bus, via the reset
button on the LCP or via a digital input.
[7]
Select setup 1 Changes the set-up upon reestablishment of
communication following a control word
timeout. If communication resumes causing
the timeout situation to disappear,
defines whether to
resume the set-up used before the timeout or
to retain the set-up endorsed by the timeout
function.
[8]
Select setup 2 See [7] Select set-up 1
[9]
Select setup 3 See [7] Select set-up 1
[10]
Select setup 4 See [7] Select set-up 1
[26]
Trip
NOTE!
The following configuration is required in order to change
the set-up after a timeout:
Set
to [9]
Multi set-up
and select the
relevant link in
Parameter Descriptions