13-03 Reset SLC
Option:
Function:
[0]
*
Do not reset SLC Retains programmed settings in all group
13 parameters (13-*).
[1]
Reset SLC
Resets all group 13 parameters (13-*) to
default settings.
3.14.3 13-1* Comparators
Comparators are used for comparing continuous variables
(i.e., output frequency, output current, analog input, etc.) to
fixed preset values.
In addition, there are digital values that will be compared to
fixed time values. See explanation in
13-10 Comparator
Operand
. Comparators are evaluated once in each scan
interval. Use the result (TRUE or FALSE) directly. All
parameters in this parameter group are array parameters
with index 0 to 5. Select index 0 to program Comparator 0,
select index 1 to program Comparator 1, etc.
13-10 Comparator Operand
Array [6]
Option:
Function:
Choices [1] to [31] are variables that will
be compared based on their values.
Choices [50] to [186] are digital values
(TRUE/FALSE) where the comparison is
based on the amount of time during
which they are set to TRUE or FALSE,
respectively. See
Select the variable to be monitored by
the comparator.
[0]
*
DISABLED
DISABLED
[0] The comparator is disabled.
[1]
Reference
Reference
[1] The resulting remote
reference (not local) as a percentage.
[2]
Feedback
Feedback
[2] In the unit [RPM] or [Hz]
[3]
Motor speed
Motor speed
[3] [RPM] or [Hz]
[4]
Motor current
Motor current
[4] [A]
[5]
Motor torque
Motor torque
[5] [Nm]
13-10 Comparator Operand
Array [6]
Option:
Function:
[6]
Motor power
Motor power
[6] [kW] or [hp]
[7]
Motor voltage
Motor voltage
[7] [V]
[8]
DC-link voltage
DC-link voltage
[8] [V]
[9]
Motor thermal
Motor thermal
[9] Expressed as a
percentage.
[10]
VLT temp.
VLT thermal
[10] Expressed as a
percentage.
[11]
Heat sink temp.
Heatsink temp
[11] Expressed as a
percentage.
[12]
Analog input
AI53
Analog input AI53
[12] Expressed as a
percentage.
[13]
Analog input
AI54
Analog input AI54
[13] Expressed as a
percentage.
[14]
Analog input
AIFB10
Analog input AIFB10
[14] [V]. AIFB10 is
internal 10 V supply.
[15]
Analog input
AIS24V
Analog input AIS24V
[15] [V] Analog input
AICCT [17] [°]. AIS24V is switch mode
power supply: SMPS 24 V.
[17]
Analog input
AICCT
Analog input AICCT [17] [°]. AICCT is
control card temperature.
[18]
Pulse input FI29
Pulse input FI29
[18] Expressed as a
percentage.
[19]
Pulse input FI33
Pulse input FI33
[19] Expressed as a
percentage.
[20]
Alarm number
Alarm number
[20] The error number.
[21]
Warning number
[22]
Analog input x30
11
[23]
Analog input x30
12
[30]
Counter A
Counter A
[30] Number of counts
[31]
Counter B
Counter B
[31] Number of counts
[50]
FALSE
False
[50] Enters the fixed value of false in
the comparator.
[51]
TRUE
True
[51] Enters the fixed value of true in
the comparator.
[52]
Control ready
Control ready
[52] The control board
receives supply voltage
[53]
Drive ready
Drive ready
[53] The adjustable frequency
drive is ready for operation and applies a
supply signal on the control board.
[54]
Running
Running
[54] The motor is running.