0-20 Display Line 1.1 Small
Option:
Function:
[1618]
Motor Thermal
Thermal load on the motor,
calculated by the ETR function.
[1619]
KTY sensor
temperature
[1620]
Motor Angle
[1621]
Torque [%] High Res.
[1622]
Torque [%]
Present motor load as a
percentage of the rated motor
torque.
[1625]
Torque [Nm] High
[1630]
DC Link Voltage
Intermediate circuit voltage in the
adjustable frequency drive.
[1632]
Brake Energy /s
Present braking energy
transferred to an external brake
resistor.
Stated as an instantaneous value.
[1633]
Brake Energy /2 min
Braking energy transferred to an
external brake resistor. The mean
power is calculated continuously
for the most recent 120 seconds.
[1634]
Heatsink Temp.
Present heatsink temperature of
the adjustable frequency drive.
The cut-out limit is 203°±9°F [95°
±5°C]; cutting back in occurs at
158°F ±9°F [70°C ± 5°C].
[1635]
Inverter Thermal
Percentage load of the inverters.
[1636]
Inv. Nom. Current
Nominal current of the adjustable
frequency drive.
[1637]
Inv. Max. Current
Maximum current of the
adjustable frequency drive.
[1638]
SL Controller State
State of the event executed by
the control.
[1639]
Control Card Temp.
Temperature of the control card.
[1650]
External Reference
Sum of the external reference as a
percentage, i.e., the sum of
analog/pulse/bus.
[1651]
Pulse Reference
Frequency in Hz connected to the
digital inputs (18, 19 or 32, 33).
[1652]
Feedback [Unit]
Reference value from
programmed digital input(s).
[1653]
Digi Pot Reference
[1657]
Feedback [RPM]
[1660]
Digital Input
Signal states form the 6 digital
terminals (18, 19, 27, 29, 32 and
33). There are 16 bits in total, but
only six of them are used. Input
0-20 Display Line 1.1 Small
Option:
Function:
18 corresponds to the leftmost of
the used bits. Signal low = 0;
Signal high = 1.
[1661]
Terminal 53 Switch
Setting
Setting of input terminal 54.
Current = 0; Voltage = 1.
[1662]
Analog Input 53
Actual value at input 53 either as
a reference or protection value.
[1663]
Terminal 54 Switch
Setting
Setting of input terminal 54.
Current = 0; Voltage = 1.
[1664]
Analog Input 54
Actual value at input 54 either as
reference or protection value.
[1665]
Analog Output 42
[mA]
Actual value at output 42 in mA.
Use
to
select the value to be shown.
[1666]
Digital Output [bin]
Binary value of all digital outputs.
[1667]
Freq. Input #29 [Hz]
Actual value of the frequency
applied at terminal 29 as an
impulse input.
[1668]
Freq. Input #33 [Hz]
Actual value of the frequency
applied at terminal 33 as an
impulse input.
[1669]
Pulse Output #27 [Hz] Actual value of impulses applied
to terminal 27 in digital output
mode.
[1670]
Pulse Output #29 [Hz] Actual value of impulses applied
to terminal 29 in digital output
mode.
[1671]
Relay Output [bin]
[1672]
Counter A
Application dependent (e.g., SLC
Control)
[1673]
Counter B
Application dependent (e.g., SLC
Control)
[1674]
Prec. Stop Counter
Display the actual counter value.
[1675]
Analog In X30/11
Actual value at input X30/11
either as reference or protection
value.
[1676]
Analog In X30/12
Actual value at input X30/12
either as reference or protection
value.
[1677]
Analog Out X30/8
[mA]
Actual value at output X30/8 in
to select the value to be
shown.
[1678]
Analog Out X45/1
[mA]
Parameter Descriptions
FC 300 Programming Guide
3-6