8-31 Address
Range:
Function:
1
*
[1 - 126 ]
Enter the address for the FC (standard) port.
Valid range: 1 - 126.
8-32 FC Port Baud Rate
Option:
Function:
Baud rate selection depends on Protocol selection in par. 8-30.
[0]
2400 Baud
[1]
4800 Baud
[2]
*
9600 Baud
[3]
19200 Baud
[4]
38400 Baud
[5]
57600 Baud
[6]
76800 Baud
[7]
115200 Baud
Default refers to the FC Protocol
8-33 Parity/Stop Bits
Option:
Function:
Parity and Stop Bits for the protocol
par. 8-30, Protocol
using the FC Port. For some of the protocols, not all
options will be visible. Default depends on the protocol selected.
[0]
Even Parity, 1 Stop Bit
[1]
Odd Parity, 1 Stop Bit
[2]
No Parity, 1 Stop Bit
[3]
No Parity, 2 Stop Bits
8-35 Minimum Response Delay
Range:
Function:
10 ms
*
[5 - 500 ms]
Specify the minimum delay time between receiving a request and transmitting a response. This is used for over-
coming modem turnaround delays.
8-36 Max Response Delay
Range:
Function:
5000 ms
*
[5 - 10000 ms]
Specify the maximum permissible delay time between transmitting a request and receiving a response. Exceeding
this delay time will cause control word time-out.
8-37 Max Inter-Char Delay
Range:
Function:
This parameter is active only when par. 8-30 is set to
FC MC
[1] protocol.
25 ms
*
[0 - 35 ms]
Specify the maximum permissible time interval between receipt of two bytes. This parameter activates time-out
if transmission is interrupted.
3.9.5. Telegram Selection, 8-40
8-40 Telegram Selection
Option:
Function:
Enables use of freely configurable telegrams or standard telegrams for the FC port.
VLT
®
HVAC Drive Programming Guide
3. Parameter Description
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
93