[41]
Reset Trip
This logic rule is TRUE if the frequency converter is tripped (but not trip-locked) and the reset button is pressed.
[42]
Auto Reset Trip
This logic rule is TRUE if the frequency converter is tripped (but not trip-locked) and an Automatic Reset is
issued.
[43]
OK Key
This logic rule is TRUE if the OK key on the LCP is pressed.
[44]
Reset Key
This logic rule is TRUE if the Reset key on the LCP is pressed.
[45]
Left Key
This logic rule is TRUE if the Left key on the LCP is pressed.
[46]
Right Key
This logic rule is TRUE if the Right key on the LCP is pressed.
[47]
Up Key
This logic rule is TRUE if the Up key on the LCP is pressed.
[48]
Down Key
This logic rule is TRUE if the Down key on the LCP is pressed.
[50]
Comparator 4
Use the result of comparator 4 in the logic rule.
[51]
Comparator 5
Use the result of comparator 5 in the logic rule.
[60]
Logic rule 4
Use the result of logic rule 4 in the logic rule.
[61]
Logic rule 5
Use the result of logic rule 5 in the logic rule.
[70]
SL Time-out 3
Use the result of timer 3 in the logic rule.
[71]
SL Time-out 4
Use the result of timer 4 in the logic rule.
[72]
SL Time-out 5
Use the result of timer 5 in the logic rule.
[73]
SL Time-out 6
Use the result of timer 6 in the logic rule.
[74]
SL Time-out 7
Use the result of timer 7 in the logic rule.
13-41 Logic Rule Operator 1
Array [6]
Select the first logical operator to use on the Boolean inputs from par. 13-40 and 13-42.
[13 -XX] signifies the boolean input of par. 13-*.
[0]
*
DISABLED
Ignores par. 13-42, 13-43, and 13-44.
[1]
AND
evaluates the expression [13-40] AND [13-42].
[2]
OR
evaluates the expression [13-40] OR [13-42].
[3]
AND NOT
evaluates the expression [13-40] AND NOT [13-42].
[4]
OR NOT
evaluates the expression [13-40] OR NOT [13-42].
[5]
NOT AND
evaluates the expression NOT [13-40] AND [13-42].
[6]
Not or
evaluates the expression NOT [13-40] OR [13-42].
[7]
Not and not
evaluates the expression NOT [13-40] AND NOT [13-42].
[8]
Not or not
evaluates the expression NOT [13-40] OR NOT [13-42].
13-42 Logic Rule Boolean 2
Array [6]
Select the second boolean (TRUE or FALSE) input for the selected logic rule.
See Parameter 13-40 for further descriptions of choices and their functions.
13-43 Logic Rule Operator 2
Array [6]
Select the second logical operator to be used on the boolean input calculated in par. 13-40, 13-41, and 13-42,
and the boolean input coming from par. 13-42.
[13-44] signifies the boolean input of par. 13-44.
[13-40/13-42] signifies the boolean input calculated in par. 13-40, 13-41, and 13-42. DISABLED [0] (factory
setting). select this option to ignore par. 13-44.
[0]
*
DISABLED
VLT
®
HVAC Drive Programming Guide
3. Parameter Description
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
121
3