[105]
Torque rel to rated
[106]
Power
[107]
Speed
[108]
Torque
[109]
Max Out Freq
[113]
Ext. Closed Loop 1
[114]
Ext. Closed Loop 2
[115]
Ext. Closed Loop 3
[139]
Bus ctrl.
[141]
Bus ctrl timeout
26-61 Terminal X42/11 Output Min. Scale
Range:
Function:
0%
*
[0.00 - 200%]
Scale the minimum output of the selected analog signal at terminal X42/11, as a percentage of the maximum
signal level. E.g. if a 0 V is desired at 25% of the maximum output value. Then programme 25%. Scaling values
up to 100% can never be higher than the corresponding setting in par 26-62.
See principle graph for parameter 6-51.
26-62 Terminal X42/11 Output Max. Scale
Range:
Function:
100%
*
[0.00 - 200%]
Scale the maximum output of the selected analog signal at terminal X42/9. Set the value to the maximum value
of the voltage signal output. Scale the output to give a voltage lower than 10V at full scale; or 10V at an output
below 100% of the maximum signal value. If 10V is the desired output current at a value between 0-100% of
the full-scale output, programme the percentage value in the parameter, i.e. 50% = 10V. If a voltage between
0 and 10V is desired at maximum output, calculate the percentage as follows:
(
10
V
desired maximum voltage
)
x100 %
i.e.
5
V : 10V
5
V x100 % = 200 %
See principle graph for parameter 6-52.
26-63 Terminal X42/11 Output Bus Control
Range:
Function:
0.00
*
[0.00 - 100%]
Holds the level of terminal X42/11 if controlled by bus.
26-64 Terminal X42/11 Output Timeout Preset
Range:
Function:
0.00%
*
[0.00 - 100%]
Holds the preset level of terminal X42/11.
In case of a bus timeout and a timeout function is selected in par 26-70 the output will preset to this level.
3. Parameter Description
VLT
®
HVAC Drive Programming Guide
230
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
3