22-32 Low Speed [RPM]
Range:
Function:
0 RPM [0.0 - par. 4.13 (Motor High
Speed Limit)]
To be used if par. 0-02,
Motor Speed Unit
, has been set for RPM (parameter not visible if Hz selected).
Set used speed for the 50% level.
This function is used for storing values needed to tune No Flow Detection.
22-33 Low Speed [Hz]
Range:
Function:
0 Hz
*
[0.0 - par. 4-14 (Motor High
Speed Limit)]
To be used if par. 0-02,
Motor Speed Unit
, has been set for Hz (parameter not visible if RPM selected).
Set used speed for the 50% level.
The function is used for storing values needed to tune No Flow Detection.
22-34 Low Speed Power [kW]
Range:
Function:
0
*
[0.0 - par. 22-38]
To be used if par. 0-03,
Regional Settings
, has been set for International (parameter not visible if North America
selected).
Set power consumption at 50% speed level.
This function is used for storing values needed to tune No Flow Detection.
22-35 Low Speed Power [Hp]
Range:
Function:
0
*
[0.0 - Par. 22-39]
To be used if par. 0-03,
Regional Settings
, has been set for North America (parameter not visible if International
selected).
Set power consumption at 50% speed level.
This function is used for storing values needed to tune No Flow Detection.
22-36 High Speed [RPM]
Range:
Function:
0 RPM
*
[0.0 - par. 4-13 (Motor High
Speed Limit)]
To be used if par. 0-02,
Motor Speed Unit
, has been set for RPM (parameter not visible if Hz selected).
Set used speed for the 85% level.
The function is used for storing values needed to tune No Flow Detection.
22-37 High Speed [Hz]
Range:
Function:
0 Hz
*
[0 - 1000 Hz]
To be used if
par. 0-02, Motor Speed Unit
has been set for Hz (parameter not visible if RPM selected).
Set used speed for the 85% level.
The function is used for storing values needed to tune No Flow Detection.
22-38 High Speed Power [kW]
Range:
Function:
0
*
[Size dependent]
To be used if
par. 0-03, Regional Settings
, has been set for International (parameter not visible if North America
selected).
Set power consumption at 85% speed level.
This function is used for storing values needed to tune No Flow Detection.
22-39 High Speed Power [Hp]
Range:
Function:
0
*
[0.0 - Max Motor Output]
To be used if par. 0-03,
Regional Settings
, has been set for North America (parameter not visible if International
selected).
Set power consumption at 85% speed level.
This function is used for storing values needed to tune No Flow Detection.
VLT
®
HVAC Drive Programming Guide
3. Parameter Description
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
177