3.9.4. 8-3* FC Port Settings
Parameters for configuring the FC Port.
8-30 Protocol
Option:
Function:
Protocol selection for the integrated FC (standard) Port (RS485) on the control card.
Parameter group 8-7* is only visible when FC Option [9] is chosen.
[0]
*
FC
Communication according to the FC Protocol as described in the
VLT HVAC Drive Design Guide, RS-485 Instal-
lation and Set-up
.
[1]
FC MC
Same as
FC
[0] but to be used when downloading SW to the frequency converter or uploading dll file (covering
information regarding parameters available in the frequency converter and their inter-dependencies) to Motion
Control Tool MCT10.
[2]
Modbus RTU
Communication according to the Modbus RTU protocol as described in the
VLT HVAC Drive Design Guide, RS-485
Installation and Set-up
.
[3]
Metasys N2
Communication protocol. The N2 software protocol is designed to be general in nature in order to accommodate
the unique properties each device may have. Please see separate manual
VLT
®
HVAC Drive Metasys, MG.
11.Gx.yy
.
[9]
FC option
To be used when a gateway is connected to the integrated RS-485 port, e.g. the BACnet gateway.
Following changes will take place:
-Address for the FC port will be set to 1 and
par. 8-31 Address
, is now used to set the address for the gateway
on the network, e.g. BACnet.
Please see separate manual
VLT
®
HVAC Drive BACnet, MG.11.Dx.yy
.
-Baud rate for the FC port will be set to a fixed value (115.200 Baud) and
par. 8-32 Baud Rate
, is now used to
set the baud rate for the network port (e.g. BACnet) on the gateway.
NB!
Further details can be found in the BACnet and Metasys manuals.
3. Parameter Description
VLT
®
HVAC Drive Programming Guide
92
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
3