5-00 Digital I/O Mode
Option:
Function:
Digital inputs and programmed digital outputs are pre-programmable for operation either in PNP or NPN systems.
[0]
*
PNP - Active at 24 V
Action on positive directional pulses (0). PNP systems are pulled down to GND.
[1]
NPN - Active at 0 V
Action on negative directional pulses (1). NPN systems are pulled up to + 24 V, internally in the frequency
converter.
This parameter cannot be adjusted while the motor is running.
5-01 Terminal 27 Mode
Option:
Function:
[0]
*
Input
Defines terminal 27 as a digital input.
[1]
Output
Defines terminal 27 as a digital output.
This parameter cannot be adjusted while the motor is running.
5-02 Terminal 29 Mode
Option:
Function:
[0]
*
Input
Defines terminal 29 as a digital input.
[1]
Output
Defines terminal 29 as a digital output.
This parameter cannot be adjusted while the motor is running.
3.7.3. 5-1* Digital Inputs
Parameters for configuring the input functions for the input terminals.
The digital inputs are used for selecting various functions in the frequency converter. All digital inputs can be set to the following functions:
Digital input function
Select
Terminal
No operation
[0]
All *term 32, 33
Reset
[1]
All
Coast inverse
[2]
All
Coast and reset inverse
[3]
All
DC-brake inverse
[5]
All
Stop inverse
[6]
All
External interlock
[7]
All
Start
[8]
All *term 18
Latched start
[9]
All
Reversing
[10]
All *term 19
Start reversing
[11]
All
Jog
[14]
All *term 29
Preset reference on
[15]
All
Preset ref bit 0
[16]
All
Preset ref bit 1
[17]
All
Preset ref bit 2
[18]
All
Freeze reference
[19]
All
Freeze output
[20]
All
Speed up
[21]
All
Speed down
[22]
All
Set-up select bit 0
[23]
All
Set-up select bit 1
[24]
All
Pulse input
[32]
term. 29, 33
Ramp bit 0
[34]
All
Mains failure inverse
[36]
All
Fire mode
[37]
All
Run Permissive
[52]
All
Hand start
[53]
All
Auto start
[54]
All
DigiPot Increase
[55]
All
DigiPot Decrease
[56]
All
DigiPot Clear
[57]
All
Counter A (up)
[60]
29, 33
Counter A (down)
[61]
29, 33
Reset Counter A
[62]
All
Counter B (up)
[63]
29, 33
Counter B (down)
[64]
29, 33
VLT
®
HVAC Drive Programming Guide
3. Parameter Description
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
65