
[84]
SL Digital Output E
See par. 13-52
SL Control Action
. The input will go high whenever the Smart Logic Action [42]
Set dig. out. E
high
is executed. The input will go low whenever the Smart Logic Action [36]
Set dig. out. E low
is executed.
[85]
SL Digital Output F
See par. 13-52
SL Control Action
. The input will go high whenever the Smart Logic Action [43]
Set dig. out. F
high
is executed. The input will go low whenever the Smart Logic Action [37]
Set dig. out. F low
is executed.
[160]
No alarm
The output is high when no alarm is present.
[161]
Running reverse
The output is high when the frequency converter is running counter clockwise (the logical product of the status
bits ‘running’ AND ‘reverse’).
[165]
Local reference active
The output is high when par. 3-13
Reference Site
= [2] Local or when par. 3-13
Reference Site
= [0]
Linked to
hand auto
at the same time as the LCP is in Hand on mode.
[166]
Remote reference ac-
tive
The output is high when par. 3-13
Reference Site = Remote
[1] or
Linked to hand/auto
[0] while the LCP is in
[Auto on] mode.
[167]
Start command active
The output is high when there is an active Start command (i.e. via digital input bus connection or [Hand on] or
[Auto on], and no Stop or Start command is active.
[168]
Drive in hand mode
The output is high when the frequency converter is in Hand on mode (as indicated by the LED light above [Hand
on].
[169]
Drive in auto mode
The output is high when the frequency converter is in Hand on mode (as indicated by the LED light above [Auto
on].
[180]
Clock Fault
The clock function has been reset to default (2000-01-01) because of a power failure.
[181]
Preventive Mainte-
nance
One or more of the Preventive Maintenance Events programmed in par. 23-10, Preventive Maintenance Item,
has passed the time for the specified action in par. 23-11, Maintenance Action.
[190]
No-Flow
A No-Flow situation or Minimum Speed situation has been detected if enabled in
Minimum Speed Detection
. par.
22-21 and/or
No-Flow Detection
, par. 22-22.
[191]
Dry Pump
A Dry Pump condition has been detected. This function must be enabled in par. 22-26, Dry Pump Function.
[192]
End of Curve
A pump running with max. speed for a period of time without reaching the set pressure has been detected. To
enable this function please see
par. 22-50 End of Curve Function
.
[193]
Sleep Mode
The frequency converter/system has turned into sleep mode. See
Sleep mode
, par. 22-4*.
[194]
Broken Belt
A Broken Belt condition has been detected. This function must be enabled in par. 22-60, Broken Belt Detection.
[195]
Bypass Valve Control
The bypass valve control (Digital / Relay output in the frequency converter) is used for compressor systems to
unload the compressor during start-up by using a bypass valve. After the start command is given the bypass
valve will be open until the frequency converter reaches
Motor speed low limit
, par. 4 -11) . After the limit has
been reached the bypass valve will be closed, allowing the compressor to operate normally. This procedure will
not be activated again before a new start is initiated and the frequency converter speed is zero during the
receiving of start signal.
Start Delay
, par. 1-71 can be used in order to delay the motor start. The Bypass valve
control principle:
[196]
Fire Mode
The frequency converter is operating in Fire Mode. See 24-0*
Fire Mode
.
[197]
Fire Mode was act.
The frequency converter has been operating in Fire Mode, but is now back in normal operation.
[198]
Drive Bypass
To be used as signal for activating an external electromechanical bypass switching the motor direct on line. See
24-1*
Drive Bypass
.
VLT
®
HVAC Drive Programming Guide
3. Parameter Description
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
71
3