[61]
Counter A (down)
(Terminal 29 or 33 only) Input for decrement counting in the SLC counter.
[62]
Reset Counter A
Input for reset of counter A.
[63]
Counter B (up)
(Terminal 29 and 33 only) Input for increment counting in the SLC counter.
[64]
Counter B (down)
(Terminal 29 and 33 only) Input for decrement counting in the SLC counter.
[65]
Reset Counter B
Input for reset of counter B.
[66]
Sleep Mode
Forces frequency converter into Sleep Mode (see par. 22-4*, Sleep Mode). Reacts on the rising edge of signal
applied!
[78]
Reset Preventive Main-
tenance Word
Resets all data in par. 16-96, Preventive Maintenance Word, to 0.
The below setting options are all related to the Cascade Controller. Wiring diagrams and settings for parameter, see group 25-** for more details.
[120]
Lead Pump Start
Starts/Stops the Lead Pump (controlled by the frequency converter). A start requires that also a System Start
signal has been applied e.g. to one of the digital inputs set for
Start
[8]!
[121]
Lead Pump Alternation Forces alternation of the lead pump in a Cascade Controller.
Lead Pump Alternation
, par. 25-50, must be set to
either
At Command
[2] or
At Staging or At Command
[3].
Alternation Event
, par. 25-51, can be set to any of
the four options.
[130 - 138]
Pump1 Interlock -
Pump9 Interlock
For the above 9 setting options, par. 25-10, Pump Interlock, must be set to
On
[1]. The function will also depend
on the setting in par. 25-05, Fixed Lead Pump. If set to
No
[0], then Pump1 refers to the pump controlled by
relay RELAY1 etc. If set to
Yes
[1], Pump1 refers to the pump controlled by the frequency converter only (without
any of the build in relays involved) and Pump2 to the pump controlled by the relay RELAY1. Variable speed pump
(lead) cannot be interlocked.
See below table:
Setting in Par. 5-1*
Setting in Par. 25-06
[0] No
[1] Yes
[130] Pump1 Interlock
Controlled by RELAY1
(only if not lead pump)
Frequency Converter controlled
(cannot be interlocked)
[131] Pump2 Interlock
Controlled by RELAY2
Controlled by RELAY1
[132] Pump3 Interlock
Controlled by RELAY3
Controlled by RELAY2
[133] Pump4 Interlock
Controlled by RELAY4
Controlled by RELAY3
[134] Pump5 Interlock
Controlled by RELAY5
Controlled by RELAY4
[135] Pump6 Interlock
Controlled by RELAY6
Controlled by RELAY5
[136] Pump7 Interlock
Controlled by RELAY7
Controlled by RELAY6
[137] Pump8 Interlock
Controlled by RELAY8
Controlled by RELAY7
[138] Pump9 Interlock
Controlled by RELAY9
Controlled by RELAY8
5-10 Terminal 18 Digital Input
Option:
Function:
[8]
*
Start
Same options and functions as par. 5-1*
Digital Inputs
, except for
Pulse input
.
5-11 Terminal 19 Digital Input
Option:
Function:
[0]
*
No operation
Same options and functions as par. 5-1*
Digital Inputs
, except for
Pulse input
.
5-12 Terminal 27 Digital Input
Option:
Function:
[2]
*
Coast Inverse
Same options and functions as par. 5-1*
Digital Inputs
, except for
Pulse input
.
3. Parameter Description
VLT
®
HVAC Drive Programming Guide
68
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark