[43]
OK Key
This event is TRUE if the OK key on the LCP is pressed.
[44]
Reset Key
This event is TRUE if the Reset key on the LCP is pressed.
[45]
Left Key
This event is TRUE if the Left key on the LCP is pressed.
[46]
Right Key
This event is TRUE if the Right key on the LCP is pressed.
[47]
Up Key
This event is TRUE if the Up key on the LCP is pressed.
[48]
Down Key
This event is TRUE if the Down key on the LCP is pressed.
[50]
Comparator 4
Use the result of comparator 4 in the logic rule.
[51]
Comparator 5
Use the result of comparator 5 in the logic rule.
[60]
Logic rule 4
Use the result of logic rule 4 in the logic rule.
[61]
Logic rule 5
Use the result of logic rule 5 in the logic rule.
[70]
SL Time-out 3
Use the result of timer 3 in the logic rule.
[71]
SL Time-out 4
Use the result of timer 4 in the logic rule.
[72]
SL Time-out 5
Use the result of timer 5 in the logic rule.
[73]
SL Time-out 6
Use the result of timer 6 in the logic rule.
[74]
SL Time-out 7
Use the result of timer 7 in the logic rule.
13-03 Reset SLC
Option:
Function:
[0]
*
Do not reset SLC
Retains programmed settings in all group 13 parameters (13-*).
[1]
Reset SLC
Resets all group 13 parameters (13-*) to default settings.
3.13.3. 13-1* Comparators
Comparators are used for comparing continuous variables (i.e. output frequency, output current, analog input etc.) to fixed preset values. In addition,
there are digital values that will be compared to fixed time values. See explanation in par. 13-10. Comparators are evaluated once in each scan interval.
Use the result (TRUE or FALSE) directly. All parameters in this parameter group are array parameters with index 0 to 5. Select index 0 to programme
Comparator 0, select index 1 to programme Comparator 1, and so on.
13-10 Comparator Operand
Array [4]
Select the variable to be monitored by the comparator.
[0]
*
DISABLED
[1]
Reference
[2]
Feedback
[3]
Motor speed
[4]
Motor current
[5]
Motor torque
[6]
Motor power
[7]
Motor voltage
[8]
DC-link voltage
[9]
Motor thermal
[10]
Drive thermal
[11]
Heat sink temp.
[12]
Analog input AI53
[13]
Analog input AI54
[14]
Analog input AIFB10
[15]
Analog input AIS24V
[17]
Analog input AICCT
3. Parameter Description
VLT
®
HVAC Drive Programming Guide
118
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
3