[12]
Out of current range
The motor current is outside the range set in par. 4-18.
[13]
Below current, low
The motor current is lower than set in par. 4-50.
[14]
Above current, high
The motor current is higher than set in par. 4-51.
[15]
Out of speed range
The output speed is outside the range set in par. 4-52 and 4-53.
[16]
Below speed, low
The output speed is lower than the setting in par. 4-52.
[17]
Above speed, high
The output speed is higher than the setting in par. 4-53.
[18]
Out of feedback range The feedback is outside the range set in par. 4-56 and 4-57.
[19]
Below feedback low
The feedback is below the limit set in par. 4-56 Warning Feedback Low.
[20]
Above feedback high
The feedback is above the limit set in par. 4-57
Warning Feedback High
.
[21]
Thermal warning
The thermal warning turns on when the temperature exceeds the limit in the motor, the frequency converter,
the brake resistor, or the thermistor.
[25]
Reverse
Reversing. Logic ‘1’ =
relay activated, 24 V DC when CW rotation of the motor. Logic ‘0’ = relay not activated,
no signal, when CCW rotation of the motor.
[26]
Bus OK
Active communication (no time-out) via the serial communication port.
[27]
Torque limit and stop
Use in performing a coasting stop and in torque limit condition. If the frequency converter has received a stop
signal and is at the torque limit, the signal is Logic ‘0’.
[28]
Brake, no warning
The brake is active and there are no warnings.
[29]
Brake ready, no fault
The brake is ready for operation and there are no faults.
[30]
Brake fault (IGBT)
The output is Logic ‘1’ when the brake IGBT is short-circuited. Use this function to protect the frequency con-
verter if there is a fault on the brake modules. Use the output/relay to cut out the main voltage from the
frequency converter.
[35]
External Interlock
External Interlock function has been activated via one of the digital inputs.
[40]
Out of ref range
[41]
Below reference low
[42]
Above reference high
[45]
Bus Ctrl
[46]
Bus Ctrl 1 if timeout
[47]
Bus Ctrl 0 if timeout
[55]
Pulse output
[60]
Comparator 0
See par. group 13-1*. If Comparator 0 is evaluated as TRUE, the output will go high. Otherwise, it will be low.
[61]
Comparator 1
See par. group 13-1*. If Comparator 2 is evaluated as TRUE, the output will go high. Otherwise, it will be low.
[62]
Comparator 2
See par. group 13-1*. If Comparator 2 is evaluated as TRUE, the output will go high. Otherwise, it will be low.
[63]
Comparator 3
See par. group 13-1*. If Comparator 3 is evaluated as TRUE, the output will go high. Otherwise, it will be low.
[64]
Comparator 4
See par. group 13-1*. If Comparator 4 is evaluated as TRUE, the output will go high. Otherwise, it will be low.
[65]
Comparator 5
See par. group 13-1*. If Comparator 5 is evaluated as TRUE, the output will go high. Otherwise, it will be low.
[70]
Logic Rule 0
See par. group 13-4*. If Logic Rule 0 is evaluated as TRUE, the output will go high. Otherwise, it will be low.
[71]
Logic Rule 1
See par. group 13-4*. If Logic Rule 1 is evaluated as TRUE, the output will go high. Otherwise, it will be low.
[72]
Logic Rule 2
See par. group 13-4*. If Logic Rule 2 is evaluated as TRUE, the output will go high. Otherwise, it will be low.
[73]
Logic Rule 3
See par. group 13-4*. If Logic Rule 3 is evaluated as TRUE, the output will go high. Otherwise, it will be low.
[74]
Logic Rule 4
See par. group 13-4*. If Logic Rule 4 is evaluated as TRUE, the output will go high. Otherwise, it will be low.
[75]
Logic Rule 5
See par. group 13-4*. If Logic Rule 5 is evaluated as TRUE, the output will go high. Otherwise, it will be low.
[80]
SL Digital Output A
See par. 13-52
SL Control Action
. The input will go high whenever the Smart Logic Action [38]
Set dig. out. A
high
is executed. The input will go low whenever the Smart Logic Action [32] Set dig. out. A low is executed.
[81]
SL Digital Output B
See par. 13-52
SL Control Action
. The input will go high whenever the Smart Logic Action [39]
Set dig. out.
Bhigh
is executed. The input will go low whenever the Smart Logic Action [33]
Set dig. out. B low
is executed.
[82]
SL Digital Output C
See par. 13-52
SL Control Action
. The input will go high whenever the Smart Logic Action [40]
Set dig. out. C
high
is executed. The input will go low whenever the Smart Logic Action [34]
Set dig. out. C low
is executed.
[83]
SL Digital Output D
See par. 13-52
SL Control Action
. The input will go high whenever the Smart Logic Action [41]
Set dig. out. D
high is executed. The input will go low whenever the Smart Logic Action [35]
Set dig. out. D low
is executed.