Troubleshooting for SA Indoor Unit - FCQG, FFQ, FHQ, FDBQ, FBQ Series
SiBE121135
286
Service Diagnosis
Troubleshooting
Note:
If
A3
is detected by the indoor unit PCB which is not mounted with X15A, the indoor unit PCB is
defective.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Connect the drain pump.
Replace the indoor unit
PCB.
Replace the drain pump.
There is a drain system
abnormality.
Connect the float switch.
Replace the float switch.
Replace the indoor unit
PCB.
(R17250)
NO
YES
NO
YES
NO
Connect the short circuit
connector.
NO
Connect the short circuit
connector.
NO
YES
YES
Replace the indoor unit
PCB.
YES
NO
YES
Is the drain
pump connected to the
indoor unit PCB?
Is the unit
a ceiling suspended
type?
NO
YES
NO
Is the drain water level
abnormally high?
YES
YES
Is the float switch
connected to X15A?
NO
Does
the drain pump work after
restarting operation?
Set to
"emergency" and
check the voltage of the
connector for the drain
pump. 220 ~ 240
VAC?
YES
Remove the float switch from
X15A, short circuit X15A, and
restart operation.
NO
Does
A3
appear on the remote
controller display?
Is the short
circuit connector
connected to X15A on the
indoor unit
PCB?
Check the
continuity of the short circuit
connector. Is there
continuity?
Is the optional
drain raising mechanism
connected?
Содержание Super Multi NX 3MKS50E3V1B
Страница 187: ...SiBE121135 RA Indoor Unit Operation Manual 175 2 1 17 Quick Reference FTXG25 35 50JV1BW A Quick Reference...
Страница 188: ...RA Indoor Unit SiBE121135 176 Operation Manual FTXS20 25K2V1B CTXS15 35K2V1B Quick Reference...
Страница 189: ...SiBE121135 RA Indoor Unit Operation Manual 177 FVXG25 35 50K2V1B Quick Reference...
Страница 246: ...SA Indoor Unit SiBE121135 234 Operation Manual 2 Start 5s 5s 5s 5s 5s End...
Страница 413: ...SiBE121135 Outdoor Unit 80 90 Class Removal Procedure 401 7 Remove the sound blanket inner Step Procedure Points R10439...