Field Settings
SiBE121135
412
Trial Operation and Field Settings
5. Field Settings
5.1
Outdoor Unit
5.1.1 Priority Room Setting
Outdoor electronic expansion valves are controlled to provide more capacity to the prioritized
room.
Setting method
Turn off the circuit breaker before changing the setting.
Only one room can be set as the priority room (By turning on one of the SW4 on the service
monitor PCB of the outdoor unit).
The control starts when all the following conditions are met.
∗
Priority room setting is made.
∗
“POWERFUL” signal from the priority room unit is received.
Note:
The operation mode of the priority room unit has precedence.
Cancellation of control
The control function is canceled when the “POWERFUL” operation mode is switched off or
20 minutes elapse after “POWERFUL Operation” started.
(R1396)
Living
room
Living
room
A
room
A
room
B
room
B
room
C
room
C
room
Normal
operation
When inverter
powerful-operation
is selected in the
priority room
The prioritized room will be heated/cooled much more quickly
Service monitor PCB
(R17271)
Priority room
setting switch (SW4)
3 or 4-room model
Service monitor PCB
5-room model
(R17272)
Priority room
setting switch (SW4)
Содержание Super Multi NX 3MKS50E3V1B
Страница 187: ...SiBE121135 RA Indoor Unit Operation Manual 175 2 1 17 Quick Reference FTXG25 35 50JV1BW A Quick Reference...
Страница 188: ...RA Indoor Unit SiBE121135 176 Operation Manual FTXS20 25K2V1B CTXS15 35K2V1B Quick Reference...
Страница 189: ...SiBE121135 RA Indoor Unit Operation Manual 177 FVXG25 35 50K2V1B Quick Reference...
Страница 246: ...SA Indoor Unit SiBE121135 234 Operation Manual 2 Start 5s 5s 5s 5s 5s End...
Страница 413: ...SiBE121135 Outdoor Unit 80 90 Class Removal Procedure 401 7 Remove the sound blanket inner Step Procedure Points R10439...