Problem Symptoms and Measures
Service Diagnosis
253
2. Problem Symptoms and Measures
Problem Symptom
Check Item
Details of Measure
Reference
Page
None of the units operates. Check the power supply.
Check if the rated voltage is supplied.
—
Check the types of the indoor units.
Check if the indoor unit type is compatible with
the outdoor unit.
—
Check the outdoor temperature.
Heating operation cannot be used when the
outdoor temperature is 20°C or higher, and
cooling operation cannot be used when the
outdoor temperature is below –10 ~ 10°C
(depending on the model).
—
Diagnose with remote controller
indication
—
267
Check the remote controller
addresses.
Check if address settings for the remote
controller and indoor unit are correct.
415
Operation sometimes
stops.
Check the power supply.
A power failure of 2 to 10 cycles can stop air
conditioner operation. (Operation lamp OFF)
—
Check the outdoor temperature.
Heating operation cannot be used when the
outdoor temperature is 20°C or higher, and
cooling operation cannot be used when the
outdoor temperature is below –10 ~ 10°C
(depending on the model).
—
Diagnose with remote controller
indication.
—
267
Some indoor units do not
operate.
Check the type of the indoor units.
Check if the indoor unit type is compatible with
the outdoor unit.
—
Diagnose with remote controller
indication
—
267
Units operate but do not
cool, or do not heat.
Check for wiring and piping errors in
the connection between the indoor
and outdoor units.
Conduct the wiring/piping error check described
on the product diagnosis nameplate.
—
Check for thermistor detection errors. Check if the thermistor is mounted securely.
—
Check for faulty operation of the
outdoor electronic expansion valve.
Set all the units to cooling operation, and
compare the temperatures of the liquid pipes to
see if the each outdoor electronic expansion
valve works.
—
Diagnose with remote controller
indication.
—
267
Diagnose by service port pressure
and operating current.
Check for refrigerant shortage.
296
Large operating noise and
vibrations
Check the output voltage of the
power module.
—
335
Check the power module.
—
—
Check the installation condition.
Check if the required spaces for installation
(specified in the installation manual) are
provided.
—
Содержание Super Multi NX 3MKS50E3V1B
Страница 187: ...SiBE121135 RA Indoor Unit Operation Manual 175 2 1 17 Quick Reference FTXG25 35 50JV1BW A Quick Reference...
Страница 188: ...RA Indoor Unit SiBE121135 176 Operation Manual FTXS20 25K2V1B CTXS15 35K2V1B Quick Reference...
Страница 189: ...SiBE121135 RA Indoor Unit Operation Manual 177 FVXG25 35 50K2V1B Quick Reference...
Страница 246: ...SA Indoor Unit SiBE121135 234 Operation Manual 2 Start 5s 5s 5s 5s 5s End...
Страница 413: ...SiBE121135 Outdoor Unit 80 90 Class Removal Procedure 401 7 Remove the sound blanket inner Step Procedure Points R10439...