Troubleshooting for Outdoor Unit
SiBE121135
296
Service Diagnosis
7. Troubleshooting for Outdoor Unit
7.1
Refrigerant Shortage
Remote
Controller
Display
U0
Outdoor Unit LED
Display
A
j
1
h
2
h
3
i
4
i
5
h
Method of
Malfunction
Detection
Refrigerant shortage detection I :
Refrigerant shortage is detected by checking the input current value and the compressor output
frequency. If the refrigerant is short, the input current is smaller than the normal value.
Refrigerant shortage detection II :
Refrigerant shortage is detected by checking the discharge pipe temperature and the opening of
the outdoor electronic expansion valve. If the refrigerant is short, the discharge pipe
temperature tends to rise.
Malfunction
Decision
Conditions
Refrigerant shortage detection I :
The following conditions continue for 7 minutes.
DC current
≤
A
× Compressor output fre
B
Output frequency >
C
Refrigerant shortage detection II :
The following conditions continue for 80 seconds.
Opening of the outdoor electronic expansion valve
≥
D
Discharge pipe temperature >
E
× target discharge pipe tempe
F
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Disconnection of the discharge pipe thermistor, indoor or outdoor heat exchanger thermistor,
room or outdoor temperature thermistor
Closed stop valve
Refrigerant shortage (refrigerant leakage)
Poor compression performance of compressor
Defective outdoor electronic expansion valve
A
(–)
B
(A)
C
(Hz)
40/50/52/58 class
0.01
0.3
54
68/75 class
0.035
0.5
55
80/90 class
0.027
2.0
40
D
(pulse)
E
(–)
F
(°C)
Cooling
450
255/256
20
Heating
40
Содержание Super Multi NX 3MKS50E3V1B
Страница 187: ...SiBE121135 RA Indoor Unit Operation Manual 175 2 1 17 Quick Reference FTXG25 35 50JV1BW A Quick Reference...
Страница 188: ...RA Indoor Unit SiBE121135 176 Operation Manual FTXS20 25K2V1B CTXS15 35K2V1B Quick Reference...
Страница 189: ...SiBE121135 RA Indoor Unit Operation Manual 177 FVXG25 35 50K2V1B Quick Reference...
Страница 246: ...SA Indoor Unit SiBE121135 234 Operation Manual 2 Start 5s 5s 5s 5s 5s End...
Страница 413: ...SiBE121135 Outdoor Unit 80 90 Class Removal Procedure 401 7 Remove the sound blanket inner Step Procedure Points R10439...