SiBE121135
Outdoor Unit: 40-75 Class
Removal Procedure
363
1.7
Removal of Distributor
Procedure
Warning
Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Step
Procedure
Points
1
Remove the putty.
Warning
Be careful not to get yourself
burnt with the pipes and other
parts that are heated by the
gas brazing machine.
Warning
If the refrigerant gas leaks
during work, ventilate the
room. (If the refrigerant gas is
exposed to flames, toxic gas
may be generated.)
Caution
From the viewpoint of global
environment protection, do
not discharge the refrigerant
gas in the atmosphere. Make
sure to collect all the
refrigerant gas.
Cautions for restoration
1. Restore the piping by non-
oxidation brazing.
2. It is required to prevent the
carbonization of the oil inside
the four way valve and the
deterioration of the gaskets
affected by heat. (Keep
below 120°C.) For the sake
of this, wrap the four way
valve with wet cloth and
provide water so that the
cloth does not dry.
In case of difficulty with gas
brazing machine
1. Disconnect the brazed part
where is easy to disconnect
and restore.
2. Cut pipes on the main unit
with a tube cutter in order to
make it easy to disconnect.
Before working, make
sure that the refrigerant
gas is empty in the circuit.
Be sure to apply nitrogen
replacement when
heating up the brazed
part.
2
Heat up and disconnect
the brazed parts to
remove the distributor.
Note:
Do not use a metal saw
for cutting pipes by all
means because the
sawdust comes into the
circuit.
When withdrawing the
pipes, be careful not to
pinch them firmly with
pliers. The pipes may get
deformed.
Provide a protective sheet
or a steel plate so that the
brazing flame cannot
influence peripheries.
(R5595)
Putty
Distributor
Brazed
parts
(R17263)
Содержание Super Multi NX 3MKS50E3V1B
Страница 187: ...SiBE121135 RA Indoor Unit Operation Manual 175 2 1 17 Quick Reference FTXG25 35 50JV1BW A Quick Reference...
Страница 188: ...RA Indoor Unit SiBE121135 176 Operation Manual FTXS20 25K2V1B CTXS15 35K2V1B Quick Reference...
Страница 189: ...SiBE121135 RA Indoor Unit Operation Manual 177 FVXG25 35 50K2V1B Quick Reference...
Страница 246: ...SA Indoor Unit SiBE121135 234 Operation Manual 2 Start 5s 5s 5s 5s 5s End...
Страница 413: ...SiBE121135 Outdoor Unit 80 90 Class Removal Procedure 401 7 Remove the sound blanket inner Step Procedure Points R10439...