Indoor Unit Control (SA Models)
SiBE121135
104
Function and Control
2.4
Hot Start Control (In Heating Operation Only)
Outline
At startup with thermostat ON or after the completion of defrosting in heating operation, the
indoor unit fan is controlled to prevent cold air from blasting out and ensure startup capacity.
Detail
TH
2
: Temperature (°C) detected with the gas thermistor
TC
: High pressure equivalent saturated temperature
Defrost ending or oil return ending
or Thermostat ON
The fan is not OFF before initiating the hot start: LL
The fan is OFF before initiating the hot start: OFF
Hot start control
Hot start in progress
Normal operation
Normal operation
H/L remote
controller setting
LL
OFF
Remote controller
setting
Level position
Fa
n
Louv
er
Hot start ending conditions
·
lapse of 3 minutes
·
[TH
2
] > 34˚C
·
Tc > 52˚C
OR
(R15421)
Содержание Super Multi NX 3MKS50E3V1B
Страница 187: ...SiBE121135 RA Indoor Unit Operation Manual 175 2 1 17 Quick Reference FTXG25 35 50JV1BW A Quick Reference...
Страница 188: ...RA Indoor Unit SiBE121135 176 Operation Manual FTXS20 25K2V1B CTXS15 35K2V1B Quick Reference...
Страница 189: ...SiBE121135 RA Indoor Unit Operation Manual 177 FVXG25 35 50K2V1B Quick Reference...
Страница 246: ...SA Indoor Unit SiBE121135 234 Operation Manual 2 Start 5s 5s 5s 5s 5s End...
Страница 413: ...SiBE121135 Outdoor Unit 80 90 Class Removal Procedure 401 7 Remove the sound blanket inner Step Procedure Points R10439...