Service Diagnosis
325
8. Check
8.1
Thermistor Resistance Check
Check No.01
Disconnect the connectors of the thermistors from the PCB, and measure the resistance of
each thermistor using tester.
The relationship between normal temperature and resistance is shown in the table and the
graphs below.
The room temperature thermistor is directly mounted on the display PCB. Remove the
display PCB from the control PCB to measure the resistance.
When the indoor heat exchanger thermistor is soldered on the PCB, remove the thermistor
and measure the resistance.
The data is for reference purpose only.
Thermistor temperature (°C)
Resistance (k
Ω
)
Room temperature thermistor
for FTXS-K and CTXS-K series
Other thermistors
–20
70.3
197.8
–15
56.1
148.2
–10
44.1
112.1
–5
34.9
85.60
0
28.2
65.93
5
22.3
51.14
10
18.1
39.99
15
14.8
31.52
20
12.2
25.02
25
10.0
20.00
30
8.3
16.10
35
6.9
13.04
40
5.8
10.62
45
4.9
8.707
50
4.1
7.176
(R25°C = 10 k
Ω
, B = 3435 K)
(R25°C = 20 k
Ω
, B = 3950 K)
Room temperature thermistor
(˚C)
50
25
0
–15
0
15
30
45
(k
Ω
)
(11952)
Other thermistors
(˚C)
(k
Ω
)
–15
0
15
30
45
150
100
50
Tester
Resistance range
(R11906)
RTH1
Tester
(R3460)
Содержание Super Multi NX 3MKS50E3V1B
Страница 187: ...SiBE121135 RA Indoor Unit Operation Manual 175 2 1 17 Quick Reference FTXG25 35 50JV1BW A Quick Reference...
Страница 188: ...RA Indoor Unit SiBE121135 176 Operation Manual FTXS20 25K2V1B CTXS15 35K2V1B Quick Reference...
Страница 189: ...SiBE121135 RA Indoor Unit Operation Manual 177 FVXG25 35 50K2V1B Quick Reference...
Страница 246: ...SA Indoor Unit SiBE121135 234 Operation Manual 2 Start 5s 5s 5s 5s 5s End...
Страница 413: ...SiBE121135 Outdoor Unit 80 90 Class Removal Procedure 401 7 Remove the sound blanket inner Step Procedure Points R10439...