Indoor Unit Control (RA Models)
SiBE121135
94
Function and Control
2. Motions (for example: in cooling)
When the microcomputer does not have a signal from the sensor in 20 minutes, it judges
that nobody is in the room and operates the unit in temperature shifted from the target
temperature. (Cooling / Dry : 2°C higher, Heating : 2°C lower, Auto : according to the
operation mode at that time.)
In case of FAN operation, the fan speed reduces by 60 rpm.
3. Airflow direction in 2-area INTELLIGENT EYE operation
Detection method: The opposite area of detected area is set as the target direction.
1. Detection signal ON in both area A and B: Shift the airflow direction to area B (left side)
2. Detection signal ON in area A: Shift the airflow direction to area B (left side)
3. Detection signal ON in area B: Shift the airflow direction to area A (right side)
4. Detection signal OFF in both area A and B: No change
* When the detection signal is OFF for 20 minutes in both area A and B, the unit starts energy
saving operation.
Others
For dry operation, you cannot set the temperature with remote controller, but internally the
target temperature is shifted.
ON
OFF
RESET.
(From area A or B)
20 min.
20 min.
ON
OFF
ON
OFF
Operation
OFF
Fan speed (
+
)
Set speed
Set speed
Target temperature
(R15308)
Remote controller
[INTELLIGENT
EYE] button
ON
OFF
INTELLIGENT EYE
lamp
within 20 minutes
Human detection
signal
Top view
Wall
Indoor unit
Area A
Area B
Left
Right
Human
(R3853)
Содержание Super Multi NX 3MKS50E3V1B
Страница 187: ...SiBE121135 RA Indoor Unit Operation Manual 175 2 1 17 Quick Reference FTXG25 35 50JV1BW A Quick Reference...
Страница 188: ...RA Indoor Unit SiBE121135 176 Operation Manual FTXS20 25K2V1B CTXS15 35K2V1B Quick Reference...
Страница 189: ...SiBE121135 RA Indoor Unit Operation Manual 177 FVXG25 35 50K2V1B Quick Reference...
Страница 246: ...SA Indoor Unit SiBE121135 234 Operation Manual 2 Start 5s 5s 5s 5s 5s End...
Страница 413: ...SiBE121135 Outdoor Unit 80 90 Class Removal Procedure 401 7 Remove the sound blanket inner Step Procedure Points R10439...