Function and Control
1.8
Automatic Operation
Outline
Automatic Cooling / Heating Function
When the automatic operation is selected with the remote controller, the microcomputer
automatically determines the operation mode as cooling or heating according to the room
temperature and the set temperature at start-up.
The unit automatically switches the operation mode to maintain the room temperature at the set
temperature.
Detail
Ts: set temperature (set by remote controller)
Tt: target temperature (determined by microcomputer)
Tr: room thermistor temperature (detected by room temperature thermistor)
C: correction value
1. The set temperature (Ts) determines the target temperature (Tt).
(Ts = 18 ~ 30°C).
2. The target temperature (Tt) is calculated as;
Tt = Ts + C
where C is the correction value
.
C = 0°C
3. Thermostat ON/OFF point and operation mode switching point are as follows.
Tr means the room thermistor temperature.
(1) Heating
→
Cooling switching point:
Tr
≥
Tt + 3.0°C (FTXG, FTXS-G, FVXG series)
Tr
≥
Tt + 2.5°C (other models)
(2) Cooling
→
Heating switching point:
Tr < Tt – 2.5°C
(3) Thermostat ON/OFF point is the same as the ON/OFF point of cooling or heating
operation.
4. During initial operation
Tr
≥
Ts: Cooling operation
Tr < Ts: Heating operation
FTXG, FTXS-G, FVXG series
Ex: When the target temperature is 25°C
Cooling
→
23°C: Thermostat OFF
→
22°C: Switch to heating
Heating
→
27°C: Thermostat OFF
→
28°C: Switch to cooling
Other Models
Ex: When the target temperature is 25°C
Cooling
→
23°C: Thermostat OFF
→
22°C: Switch to heating
Heating
→
26.5°C: Thermostat OFF
→
27.5°C: Switch to cooling
Target tempe 3.0˚C
Heating Operation
Target temperature – 2.5˚C
Cooling Operation
(R11892)
Target temperature – 2.0˚C
= Thermostat OFF
Target tempe 2.0˚C
= Thermostat OFF
(R11893)
Target tempe 2.5˚C
Heating Operation
Target temperature – 2.5˚C
Cooling Operation
Target temperature – 2.0˚C
= Thermostat OFF
Target tempe 1.5˚C
= Thermostat OFF
Содержание Super Multi NX 3MKS50E3V1B
Страница 187: ...SiBE121135 RA Indoor Unit Operation Manual 175 2 1 17 Quick Reference FTXG25 35 50JV1BW A Quick Reference...
Страница 188: ...RA Indoor Unit SiBE121135 176 Operation Manual FTXS20 25K2V1B CTXS15 35K2V1B Quick Reference...
Страница 189: ...SiBE121135 RA Indoor Unit Operation Manual 177 FVXG25 35 50K2V1B Quick Reference...
Страница 246: ...SA Indoor Unit SiBE121135 234 Operation Manual 2 Start 5s 5s 5s 5s 5s End...
Страница 413: ...SiBE121135 Outdoor Unit 80 90 Class Removal Procedure 401 7 Remove the sound blanket inner Step Procedure Points R10439...