SiBE121135
Indoor Unit Control (RA Models)
Function and Control
87
1.9
Thermostat Control
Thermostat control is based on the difference between the room thermistor temperature and the
target temperature.
Thermostat OFF Condition
The temperature difference is in the zone A.
Thermostat ON Condition
The temperature difference returns to the zone C after being in the zone A.
The system resumes from defrost control in any zones except A.
The operation turns on in any zones except A.
The monitoring time has passed while the temperature difference is in the zone B.
(Cooling / Dry : 10 minutes, Heating / Radiant : 10 seconds)
<Cooling / Dry>
Wall Mounted Type, Floor Standing Type
Floor / Ceiling Suspended Dual Type, Duct Connected Type
B
A
OFF
ON
C
Room thermistor temperature – target temperature
–1.5˚C
(R12319)
Cooling : –0.5˚C
Dry : –0.5˚C
Cooling : –2.0˚C
Dry : –2.5 ~ –2.0˚C
B
B
A
A
OFF
OFF
ON
ON
C
C
Room thermistor temperature – target temperature
–1.5˚C
(R12391)
Cooling : –2.0˚C
Dry : –2.5 ~ –2.0˚C
Cooling : –1.0˚C
Dry : –1.0˚C
Содержание Super Multi NX 3MKS50E3V1B
Страница 187: ...SiBE121135 RA Indoor Unit Operation Manual 175 2 1 17 Quick Reference FTXG25 35 50JV1BW A Quick Reference...
Страница 188: ...RA Indoor Unit SiBE121135 176 Operation Manual FTXS20 25K2V1B CTXS15 35K2V1B Quick Reference...
Страница 189: ...SiBE121135 RA Indoor Unit Operation Manual 177 FVXG25 35 50K2V1B Quick Reference...
Страница 246: ...SA Indoor Unit SiBE121135 234 Operation Manual 2 Start 5s 5s 5s 5s 5s End...
Страница 413: ...SiBE121135 Outdoor Unit 80 90 Class Removal Procedure 401 7 Remove the sound blanket inner Step Procedure Points R10439...