SiBE121135
Troubleshooting for Outdoor Unit
Service Diagnosis
309
7.11 Discharge Pipe Temperature Control
Remote
Controller
Display
F3
Outdoor Unit LED
Display
A
j
1
i
2
h
3
i
4
h
5
h
Method of
Malfunction
Detection
Detected by the discharge pipe thermistor
Malfunction
Decision
Conditions
If the temperature detected by the discharge pipe thermistor rises above
A
°C, the
compressor stops.
The error is cleared when the discharge pipe temperature is dropped below
B
°C.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Defective discharge pipe thermistor
(Defective outdoor heat exchanger thermistor or outdoor temperature thermistor)
Defective outdoor electronic expansion valve or coil
Refrigerant shortage
Defective four way valve
Water mixed in refrigerant
Defective stop valve
Defective outdoor unit PCB
Troubleshooting
Check No.01
Refer to P.325
Check No.12
Refer to P.329
Check No.14
Refer to P.330
A
(°C)
B
(°C)
40/50/52/58 class
110
95
68/75/80/90 class
120
107
(R15286)
Caution
NG
OK
OK
OK
NG
NG
∗
Discharge pipe thermistor
∗
Outdoor heat exchanger thermistor
∗
Outdoor temperature thermistor
∗
Refrigerant shortage
∗
Four way valve
∗
Water mixed
∗
Stop valve
Check No. 01
Check the thermistors.
Check No. 14
Check the refrigerant
line.
Check No. 12
Check the outdoor electronic
expansion valve.
Replace the
defective
thermistor.
Replace the outdoor
electronic expansion valve
or the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание Super Multi NX 3MKS50E3V1B
Страница 187: ...SiBE121135 RA Indoor Unit Operation Manual 175 2 1 17 Quick Reference FTXG25 35 50JV1BW A Quick Reference...
Страница 188: ...RA Indoor Unit SiBE121135 176 Operation Manual FTXS20 25K2V1B CTXS15 35K2V1B Quick Reference...
Страница 189: ...SiBE121135 RA Indoor Unit Operation Manual 177 FVXG25 35 50K2V1B Quick Reference...
Страница 246: ...SA Indoor Unit SiBE121135 234 Operation Manual 2 Start 5s 5s 5s 5s 5s End...
Страница 413: ...SiBE121135 Outdoor Unit 80 90 Class Removal Procedure 401 7 Remove the sound blanket inner Step Procedure Points R10439...