fig. 61 Error read outs
LT.AL.W7H.000.064
4.4.2 Deleting errors
The last message in the list, Er followed by cl will appear in the display;
•
Press the
[enter]
-key again, and the following will appear in the display:
[0]
;
•
Press the
[+]
-key to set the parameter to
[1]
;
•
Press the
[enter]
-key, to delete the error memory;
•
Press the
[escape]
-key twice to exit the error memory.
When tracing an error, the cause can often be found more quickly if the
operating status at the time the error occurred can be retrieved from the error
memory.
page 49
5 SERVICE PARTS SERVICE PARTS
5.1 General
If, following the annual inspection or maintenance any part of the boiler is found to
need replacing, use Remeha spare parts only or spare parts and materials
recommended by Remeha.
If any component is to be replaced and it is covered by the terms and condition as
described in the warranty leaflet return the faulty component to Remeha with the
details as shown in table 13.
Содержание Avanta 12v
Страница 15: ...fig 05 Mounting the Avanta 59970 LT GB W7H 002 page 8 2 3 Water side connections 2 3 1 Water flow ...
Страница 34: ...fig 16 Connecting external controls R000158 A page 18 ...
Страница 35: ......
Страница 63: ...fig 42 Read out settings LT AL W7H 000 046 ...
Страница 68: ...fig 43 Change parameters in service level LT AL W7H 000 047 ...
Страница 70: ...fig 44 Change boiler output LT AL W7H 000 048 ...
Страница 87: ...fig 59 Assembling the boiler 59970LTGBW7H031 page 44 4 ERRORS 4 1 General ...
Страница 96: ......
Страница 99: ...fig 62 Exploded view Remeha Avanta 59970EVGBW7H010 ...
Страница 108: ...page 60 ...
Страница 109: ...page 61 ...