The boiler will automatically return to the normal operating mode if no keys
are pressed for 10 minutes.
page 36
2.10.9 Changing the maximum output (Hi) for CH operation
The maximum output for CH operation can be changed with
parameter
[P][1][7]
(maximum fan speed) and is set standard to a speed of 2400,
3000, 3500, 4500 or 5200 rpm for the five System-types. See the speed-input
ratio
This parameter can be changed from the stand-by status as follows:
• Press the
[enter]
-key and briefly the
[reset]
-key until codes
[C]
and
[0]
appear
alternately in the display;
• Press the
[+]
-key until access code
[1][2]
is displayed;
• Press the
[enter]
-key until
[P][1]
appears (codes
[P]
and
[1]
are displayed
alternately);
• Press the
[+]
-key to go to parameter
[1][7]
;
• Press the
[enter]
-key until
[P][1][7]
appears (codes
[P]
and
[1][7]
are displayed
alternately);
• Press the
[+]
or
[-]
key to change this value for Avanta 18v, for example
to
[3][5]
(3500 rpm corresponds with 18kW);
• Press
[enter]
-key to confirm the value;
• Press
[reset]
-key to return to the operating mode.
Содержание Avanta 12v
Страница 15: ...fig 05 Mounting the Avanta 59970 LT GB W7H 002 page 8 2 3 Water side connections 2 3 1 Water flow ...
Страница 34: ...fig 16 Connecting external controls R000158 A page 18 ...
Страница 35: ......
Страница 63: ...fig 42 Read out settings LT AL W7H 000 046 ...
Страница 68: ...fig 43 Change parameters in service level LT AL W7H 000 047 ...
Страница 70: ...fig 44 Change boiler output LT AL W7H 000 048 ...
Страница 87: ...fig 59 Assembling the boiler 59970LTGBW7H031 page 44 4 ERRORS 4 1 General ...
Страница 96: ......
Страница 99: ...fig 62 Exploded view Remeha Avanta 59970EVGBW7H010 ...
Страница 108: ...page 60 ...