If the display is blank (should show red dots or letters), check:
- 230 V main supply available to switch spur;
- switch spur fuse;
- cable and connections between the switched spur and the boiler control unit;
- fuse on the boiler control unit (F2 = 2AT, 230V).
•
An error code appearing in the display can be recognised as follows:
[E][1][0]
, (the display alternately shows an
[E]
and a number e.g.
[1][0]
). The
meaning of this error codes can be found in the error table, see
• Resolve the error first if possible.
• Press the
[reset]
-key and hold for at least 1 second to restart the boiler.
page 32
After any error
[E][1]
,
[E][2]
,
[E][7]
,
[E][1][0]
or
[E][1][3]
; the 3 minute
venting cycle will run first before starting the boiler.
• Checking CH function;
- Ensure the time control is in the CH on position
- Set the room thermostat on a high demanding temperature and, the display shows:
[1]
pre-purge stage;
[2]
Ignition stage;
[3]
operating in CH mode.
- Set the room thermostat back to a lower temperature (no more heat demand), the display shows;
[5]
waiting-time; 3 to 10 minutes (only when flow temperature has already been reached and heating demand is
still existing);
[1]
pre-purge stage;
[6]
pump run on after CH or DHW is satisfied;
[0]
stand-by mode.
2.10.6 Read out settings
The following settings can be read out in the 'user menu':
-
[t][1]
= flow temperature [°C];
-
[t][2]
= return temperature [°C];
-
[t][3]
= calorifier temperature [°C];
-
[t]
[
4]
= outside temperature [°C];
-
[F][L]
= ionisation current [µA];
-
[F]
= fan speed [rpm];
•
Press the
[+]
-key, until
[t][1]
appears and, for example,
[6][8]
(68°C), the
current flow temperature;
Содержание Avanta 12v
Страница 15: ...fig 05 Mounting the Avanta 59970 LT GB W7H 002 page 8 2 3 Water side connections 2 3 1 Water flow ...
Страница 34: ...fig 16 Connecting external controls R000158 A page 18 ...
Страница 35: ......
Страница 63: ...fig 42 Read out settings LT AL W7H 000 046 ...
Страница 68: ...fig 43 Change parameters in service level LT AL W7H 000 047 ...
Страница 70: ...fig 44 Change boiler output LT AL W7H 000 048 ...
Страница 87: ...fig 59 Assembling the boiler 59970LTGBW7H031 page 44 4 ERRORS 4 1 General ...
Страница 96: ......
Страница 99: ...fig 62 Exploded view Remeha Avanta 59970EVGBW7H010 ...
Страница 108: ...page 60 ...
Страница 109: ...page 61 ...