fig. 09 Connecting CH flow
59970.LT.GB.W7H.007
page 12
2.3.12 Connecting condensate drain
•
Connect the condensate drain outlet
to a suitable waste water drain point
using acid resisting pipe work (i.e. - ¾" overflow). To enable the siphon in the
boiler to be removed / serviced, the connection should not be a permanent
one (i.e. "push fit" system or a "tundish" immediately below the boiler).
•
To prevent the risk of freezing connect the condensate into an internal vertical
soil pipe using a tundish (air break) c/w a min 75 mm water seal trap.
•
If the condensate pipe has to run externally make sure this is done by
realizing the shortest possible route, and increase the diameter to at least 1¼"
or insulate it with weather resistant insulation.
•
The drain should slope at least 3 cm per meter, with a maximum horizontal
length of 5 m.
Содержание Avanta 12v
Страница 15: ...fig 05 Mounting the Avanta 59970 LT GB W7H 002 page 8 2 3 Water side connections 2 3 1 Water flow ...
Страница 34: ...fig 16 Connecting external controls R000158 A page 18 ...
Страница 35: ......
Страница 63: ...fig 42 Read out settings LT AL W7H 000 046 ...
Страница 68: ...fig 43 Change parameters in service level LT AL W7H 000 047 ...
Страница 70: ...fig 44 Change boiler output LT AL W7H 000 048 ...
Страница 87: ...fig 59 Assembling the boiler 59970LTGBW7H031 page 44 4 ERRORS 4 1 General ...
Страница 96: ......
Страница 99: ...fig 62 Exploded view Remeha Avanta 59970EVGBW7H010 ...
Страница 108: ...page 60 ...
Страница 109: ...page 61 ...