Boiler type
Fan speed (rpm)
O
2
CO
2
Full load
[H][3]
*
%
%
12v
approx. 2400
5.1 ± 0.1
10.3 ± 0.1
15v
approx. 2800
5.1 ± 0.1
10.3 ± 0.1
18v
approx. 3300
5.1 ± 0.1
10.3 ± 0.1
24v
approx. 4300
5.1 ± 0.1
10.3 ± 0.1
30v
approx. 5000
5.1 ± 0.1
10.3 ± 0.1
table 06 Setting values full load CO
2
and O
2
(front panel not fitted)
* On forced full load, the 2nd digit indicates the operating code
page 29
•
Unscrew the flue gas sampling cap and connect the flue gas analyser.
•
Set boiler to full load: Press the
[enter]
-key, keep it pressed and also press
the
[+]
-key until
[H][3]
appears in the display; full load has been set.
•
Once the unit has reached the full-load fan speed, measure the O
2
/CO
2
-
percentage and compare this to the values in
•
If the values are not in accordance with the table then correct the gas /air ratio
controls using the adjusting screw A on the gas block.
•
If the value is too low turn the screw A anti clockwise this increases the gas
rate - if the value is too high turn the screw clockwise which decreases the
gas rate
•
Check the flame through the sight glass which should be stable with a regular
blue distribution.
Only make small adjustments to the adjusting screw, maximum 1/8 turns
when setting O
2
/CO
2
Ensure that the analysing probe has a gas tight seal in the sampling point
with the probe end in the centre of the flue duct.
5.
Setting the gas/air ratio at part load
Setting values O
2
/CO
2
for natural gas
Boiler type
Fan speed (rpm)
O
2
CO
2
Part load
[L][3]
*
%
%
12v
approx. 1300
5.2 ± 0.1
8.8 ± 0.1
15v
approx. 1300
5.2 ± 0.1
8.8 ± 0.1
18v
approx. 1300
5.2 ± 0.1
8.8 ± 0.1
24v
approx. 1300
5.2 ± 0.1
8.8 ± 0.1
Содержание Avanta 12v
Страница 15: ...fig 05 Mounting the Avanta 59970 LT GB W7H 002 page 8 2 3 Water side connections 2 3 1 Water flow ...
Страница 34: ...fig 16 Connecting external controls R000158 A page 18 ...
Страница 35: ......
Страница 63: ...fig 42 Read out settings LT AL W7H 000 046 ...
Страница 68: ...fig 43 Change parameters in service level LT AL W7H 000 047 ...
Страница 70: ...fig 44 Change boiler output LT AL W7H 000 048 ...
Страница 87: ...fig 59 Assembling the boiler 59970LTGBW7H031 page 44 4 ERRORS 4 1 General ...
Страница 96: ......
Страница 99: ...fig 62 Exploded view Remeha Avanta 59970EVGBW7H010 ...
Страница 108: ...page 60 ...
Страница 109: ...page 61 ...