Before installation, check that the gas meter has sufficient capacity for the
demand. Remember to consider the consumption of all household appliances.
2.4.2 Adjusting boiler to other gas-type
The Avanta boiler is suitable for both natural gas and propane firing. For propane a
kit with restrictor is required. The boiler is supplied as standard set for natural gas
(G20), therefore the following procedure must be carried out BEFORE the boilers are
fired and commissioned for the first time on propane:
- Fit restrictor (not included with boiler)
- Adjust the fan speed (see
) and adjust the gas/air ratio (see
page 13
2.4.3 Connecting the gas supply
•
Before starting any work on the gas supply, turn off the main isolation valve.
•
Remove the dust cap from the gas connection
at the bottom of the boiler.
•
Connect the gas supply to the 22 mm Øconnection (copper tail supplied).
•
Make sure there is no dirt in the gas pipe.
•
Make sure that there is sufficient gas pressure available (at full load > 17
mbar).
•
Preferably install a gas filter in the gas pipe to protect the boiler.
•
The gas supply must be connected, tested for soundness and purged by a
qualified Engineer and in accordance with BS 6891.
Содержание Avanta 12v
Страница 15: ...fig 05 Mounting the Avanta 59970 LT GB W7H 002 page 8 2 3 Water side connections 2 3 1 Water flow ...
Страница 34: ...fig 16 Connecting external controls R000158 A page 18 ...
Страница 35: ......
Страница 63: ...fig 42 Read out settings LT AL W7H 000 046 ...
Страница 68: ...fig 43 Change parameters in service level LT AL W7H 000 047 ...
Страница 70: ...fig 44 Change boiler output LT AL W7H 000 048 ...
Страница 87: ...fig 59 Assembling the boiler 59970LTGBW7H031 page 44 4 ERRORS 4 1 General ...
Страница 96: ......
Страница 99: ...fig 62 Exploded view Remeha Avanta 59970EVGBW7H010 ...
Страница 108: ...page 60 ...
Страница 109: ...page 61 ...