C200H AC Servo Manual
101
No.
Alarm
name
Running state
Reason
Processing method
2
Main
circuit
overvolta
ge
Appears when
the control
power is
turned on
Circuit board failure.
Replace the servo driver.
Appears when
the main
power is
turned on
1. The power supply
voltage is too high.
2. The power supply
voltage waveform is
abnormal.
Check the power supply.
Appears
during motor
operation
The brake resistance wiring
is disconnected.
Rewire.
1. The brake transistor is
damaged.
2. The internal braking
resistance is damaged.
Replace the servo driver.
Insufficient capacity of
braking circuit.
1. Reduce the start and stop
frequency.
2. Increase the acceleration
and deceleration time
constant.
3. Reduce the torque limit.
4. Reduce load inertia.
5. Replace the driver and
motor with higher power.
Содержание C200H Series