CRS-500 1:N Redundancy System
Revision 4
Serial Interface Operation
10–17
MN-CRS-500
Parameter
Type
Controller-to-Target
Instruction Code and Qualifier Arguments for
Command or
Query
Description of Arguments
(Note that all arguments are ASCII numeric codes – i.e.,
ASCII codes between 48 and 57)
Target-to-Controller
Command
Query
Response to
Command
Response to Query
(see Description of
Arguments)
NTP Primary
Server
NSP=
NSP?
15 bytes
Command or Query.
Sets or returns the NTP (Network Time Protocol) Primary Server Address in the
form aaa.bbb.ccc.ddd, where:
aaa = 000 to 223
bbb = 000 to 255
ccc = 000 to 255
ddd = 000 to 255
NOTES:
1)
Permitted ranges as specified above CANNOT BE ALL ZEROES.
2)
The NTP Primary Server Address can be cleared by setting it to 0.0.0.0
COMMAND EXAMPLE: <0000/NSP=010.006.030.001{CR}
NSP=
NSP?
NSP*
NSP#
NSP=xxx.xxx.xxx.xxx
NTP
Secondary
Server
NSS=
NSS?
15 bytes
Command or Query.
Sets or returns the NTP Secondary Server Address in the form aaa.bbb.ccc.ddd
where:
aaa = 000 to 223
bbb = 000 to 255
ccc = 000 to 255
ddd = 000 to 255
NOTES:
1)
Permitted ranges as specified above CANNOT BE ALL ZEROES.
2)
The NTP Secondary Server Address can be cleared by setting it to 0.0.0.0
COMMAND EXAMPLE: <0000/NSS=010.006.030.002{CR}
NSS=
NSS?
NSS*
NSS#
NSS=xxx.xxx.xxx.xxx
Number of
Unread Stored
Events
N/A
NUE?
3 bytes
Query only.
Sets or returns the number of Stored Events that remain unread, in the form xxx.
NOTE: This means unread over the remote control. Viewing the stored events
from the CSU front panel does not affect this value.
QUERY RESPONSE EXAMPLE: >0000/NUE=098{CR}{LF}
N/A
NUE=xxx
Read Next 5
Unread Stored
Events
N/A
RNE?
80 bytes
Query only.
Returns the oldest 5 Stored Events that have not yet been read over the remote
control in the form [cr]Sub-body[cr]Sub-body[cr]Sub-body[cr]Sub-body[cr]Sub-
body, where:
Sub-body = KLMddmmyyhhmmss, where:
K = Fault/clear indicator, where F = Fault; C = Clear; I = Info
L = Faulting/clearing unit, where value = 1 through 9 (TM 1 through TM 9), A
(TM 10), B (RM1), C (Switch), or D (Info)
N/A
RNE=[cr]KLMddmmyyh
hmmss[cr]KLMddmmyy
hhmmss[cr]KLMddmmy
yhhmmss[cr]KLMddmm
yyhhmmss[cr]KLMddm
myyhhmmss
Содержание CRS-500
Страница 24: ...CRS 500 1 N Redundancy System Revision 4 Preface x MN CRS 500 Notes...
Страница 38: ...CRS 500 1 N Redundancy System Revision 4 Introduction 1 14 MN CRS 500 BLANK PAGE...
Страница 54: ...CRS 500 1 N Redundancy System Revision 4 Checklists for Initial Start up and Configuration 3 6 MN CRS 500 Notes...
Страница 60: ...CRS 500 1 N Redundancy System Revision 4 Installation 4 6 MN CRS 500 BLANK PAGE...
Страница 164: ...CRS 500 1 N Redundancy System Revision 4 Ethernet Interface Operation 9 22 MN CRS 500 BLANK PAGE...
Страница 184: ...CRS 500 1 N Redundancy System Revision 4 Serial Interface Operation 10 20 MN CRS 500 BLANK PAGE...
Страница 216: ...CRS 500 1 N Redundancy System Revision 4 Appendix C C 4 MN CRS 500 Figure C 2 External EIA 485 with CDM 625 A Modems...
Страница 219: ......
Страница 220: ...2114 WEST 7TH STREET TEMPE ARIZONA 85281 USA 480 333 2200 PHONE 480 333 2161 FAX...