Setpoint group
Engine parameters
Related FW
2.6.0
Range [units]
0 .. 600 [s]
Default value
30
Step
1 s
Comm object
8258
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Runtime of the unloaded engine to cool the engine before stop.
Cooling Time
Setpoint group
Engine parameters
Related FW
2.6.0
Range [units]
0 .. 3600 [s]
Default value
120
Step
1 s
Comm object
8662
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Runtime of engine after cooling pump. The binary output Cooling pump closes when engine starts and opens
AfterCoolTime delayed after the engine comes to quiet state - RPM = 0.
Note:
If the engine After cooling function is needed the binary output COOLING PUMP should be
configured.
AfterCoolTime