ID-Mobile Global Guide
69
Setpoint group
Basic settings
Related FW
2.6.0
Range [units]
[PRIMARY, SECONDARY, BIN.INPUT]
Default value
PRIMARY
Step
Comm object
10231
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Activates/deactivates the logical binary output “Second RPM Sw” see Logical BO in table below. This output
can be configured to J1939 output to switch ECU Nominal RPM.
BIN.INPUT: PRIMARY / SECONDARY Nominal RPM is selected via Binary input “BI Secondary Sw”.
Setpoint name
Setpoint setting
Logical BO
Logical BI
Governor mode
ISOCH / DROOP / BIN.INPUT
Droop Sw
BI Droop
Speed select
PRIMARY / SECONDARY / BIN.INPUT
Second RPM Sw
BI Secondary
Idle/Nominal
IDLE / NOMINAL / BIN.INPUT
Nominal Sw
BI Nominal
Note:
Basic setting: Nominal RPM must correspond to ECU Nominal RPM for 100% Throttle position in
AS and 50% in SS.
Speed Select (SS only)
Setpoint group
Basic settings
Related FW
2.6.0
Range [units]
[hh:mm:ss]
Default value
00:00:00
Step
Comm object
10042
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Timer ON