ID-Mobile Global Guide
253
Force protection
Symbol
Inputs
Input
Type
Range[DIM]
Function
Lvl 1
B
N/A
The input activates yellow
level of the configured
protection if it is configured.
Lvl 2
B
N/A
The input activates red
level of the configured
protection if a red level
protection is configured.
Fls
B
N/A
The input activates sensor
fail if a red level protection
is configured.
Outputs
Description
This block issues alarms of configured type and text when appropriate binary input is
activated.
1. Select the protection type from the list.
2. Enter the message, which will appear in the Alarmlist together with the prefix
according to protection type when the protection is activated.
3. Go back to the drawing and attach wires to the inputs. Inputs are enabled and disabled
according to selected protection type (e.g. if warning is selected, then "Lvl 2" input is
disabled). Because of this the protection type must be configured first and then wires
can be attached.
Note:
The inputs are assigned to their sources in the sheet by
dragging a wire
from the
input to the source.