ID-Mobile Global Guide
168
Source: Log Bout
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
275
Description
Function is based on Binary output COMMON ALARM - stays closed when any alarm is active (at least one
item in Alarm list) and opens for 2 sec when any new Alarm is activated. The first activation is delayed 2 sec.
No Fault reset influence when at least one alarm is active. Output opens when Alarm list is empty.
Alarm Blink
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
278
Description
Alarm indication:
Output starts switching (blinking 0.5 / 0.5 sec from opened or closed state) when any new alarm
comes
Output stays closed after Fault reset when any alarm is still active
Output opens after Fault reset when no alarm is active
Alarm BlinkAct
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
2
Description
The output closes if any alarm is activated and opens after Fault reset even if the Alarm is still active.
Alarm
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
352
Description
Indication of Binary output 1 and/or Binary output 2 fail or Broken wire detection.
BO 1/2 Fail
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
353
Description
Indication of Binary output 3 and/or Binary output 4 fail or Broken wire detection.
BO 3/4 Fail