ID-Mobile Global Guide
79
Setpoint group
Engine parameters
Related FW
2.6.0
Range [units]
1 .. 6000 [s]
Default value
2
Step
1 s
Comm object
8394
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Time the binary output PRE-START is active prior to engine start (Start request sending to ECU). Set to
zero if you want to start immediately after Start button is pressed (the PRE-START output stays opened).
RPM must be zero during Prestart time otherwise the Starting procedure is not activated.
Prestart Time
Setpoint group
Engine parameters
Related FW
2.6.0
Range [units]
1 .. 200 [s]
Default value
20
Step
1 s
Comm object
8256
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Amount of time the controller will crank the engine in an attempt to start.
Note:
The InteliDrive stops cranking after three seconds when RPM = 0.
MaxCrank Time
Setpoint group
Engine parameters
Related FW
2.6.0
Range [units]
1 .. 200 [s]
Default value
8
Step
1 s
Comm object
8257
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Pause between crank attempts.
CrnkFail Pause