ID-Mobile Global Guide
141
8.1.4 Logical binary inputs
What Logical binary inputs are:
Any InteliDrive controller binary input can be configured as “function” and/or “protection”. Following chapter
contains Logical binary inputs list (functions list) that can be configured to any physical input.
Note:
Minimal input pulse duration is 120 ms to be detected as valid (binary inputs sampling rate is 100 ms).
Adjustable delay can be configured to any binary input when is used as a protection: Standard = 0,5 sec or one
of BinInp delay 1, 2, 3 that can be adjusted by corresponding Setpoint BinInp delay 1, 2, 3.
BI delay configuration
Setpoint
Standard (0.5s)
BinInp delay 1
BinInp delay 1
BinInp delay 2
BinInp delay 2
BinInp delay 3
BinInp delay 3
Alphabetical groups of Logical binary inputs
For full list of Logical binary inputs go to the chapter