ID-Mobile Global Guide
67
Setpoint group
Basic settings
Related FW
2.6.0
Range [units]
0 .. 60000 [ppl]
Default value
1
Step
1
Comm object
11566
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Conversion constant (number of pulses for increment by 1) from IM2 impulse input to Imp1 value. Frequency
range is max 300 Hz.
Example:
To measure e.g. actual water flow in liters (or cubic meter) per minute set TransferRate =
10 [ ] when sensor gives 10 pulses per liter (or cubic meter).
Example:
To measure total water consumption in liters (or cubic meter) set TransferRate = 100 [ ]
when sensor gives 100 pulses per 1liter (or cubic meter).
Pulses/Litre 2
Setpoint group
Basic settings
Related FW
2.6.0
Range [units]
430 .. 3000 [Hz]
Default value
1200
Step
1 Hz
Comm object
10911
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Frequency of PWM signal on Speed Governor Output.
Note:
Corresponding hardware jumper SGGO has to be switched to PWM position.
SpdGovPWM Rate