Max
continuous
current
(single
channel)
3A
Peak current
(single
channel)
4A
Max
continuous
current BO9
to BO16
4×2A
Maximum
switching
voltage
36VDC
BO9 to BO16
Number of
inputs
16 (8 common pins with Analog
outputs)
Resolution
10 bits
Jumper
selectable
range (AIN1 –
AIN16)
20mA, 5 VDC, 24VDC, 2,5kΩ, PT1000
Maximal
resistance
range
25 kΩ
Maximal
voltage range
38 V
Maximal
current range
22 mA
Input
impedance
180 Ω for mA measuring
Input
impedance
> 100 kΩ for V measuring
Resistance
measurement
tolerance
± 2 % ± 2 Ω out of measured value
Voltage
measurement
tolerance
± 2 % ± 1mV out of measured value
Current
measurement
tolerance
± 2 % ± 0,5mA out of measured value
Analog inputs
Number of
outputs
8 common pins with Analogue inputs
(AI9-AI16)
Resolution
10 bits
Jumper
selectable
range (AIN9 –
AIN16)
20mA, 10 VDC, 24VDC
Analog outputs
Note:
Restriction for HW version
1.2 and lower:
power supply must be more than
18VDC to achieve full range of
AOUT
Maximal
current
loading
10 mA
Voltage
output
tolerance
± 2 % ± 0.1V out of measured value
Current
output
tolerance
± 2 % ± 0,5mA out of measured value
Number of
outputs
1
Jumper
selectable
range
±10 VDC
±10VDC via 10 kΩ
PWM (430 – 3.000 Hz, step 1Hz)
Governor output
Number of
inputs
4
Type of
sensor
magnetic pick-up (connection by
shielded cable is recommended)
Input
impedance
10 kΩ
Minimum
input voltage
2 Vpk-pk (from 4Hz to 4kHz)
Maximum
input voltage
50 Veff
Minimum
measured
frequency
4 Hz
Maximum
measured
frequency
10 kHz (min. input voltage 6Vpk-pk)
Frequency
measurement
tolerance
1.5 %
Speed pick-up input
Max. D+
output
current
300 mA
Guaranteed
level for
signal
Charging OK
90% of supply voltage
D+ funcion
ID-Mobile Global Guide
56