ID-Mobile Global Guide
84
Setpoint group
Engine parameters
Related FW
2.6.0
Range [units]
[ENABLED / CHRGFAIL / DISABLED]
Default value
DISABLED
Step
Comm object
9683
Related applications
Config level
Standard
Setpoint visibility
Always
Description
ENABLED
The D+ terminal is used for both functions – “running engine” detection and charge fail
detection.
CHRGFAIL
The D+ terminal is used for charge fail detection only
DISABLED
The D+ terminal is not used.
Note:
The magnetization current is provided independently on this setpoint value.
D+ function
Setpoint group
Engine parameters
Related FW
2.6.0
Range [units]
[DIESEL / GAS]
Default value
DIESEL
Step
Comm object
9100
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Selecting of FUEL SOLENOID output function.
DIESEL
Output closes together with Binary output STARTER.
The output opens if Emergency stop comes or Cooled engine is stopped and in pause between
repeated starts.
GAS
Ignition is activated (binary output Ignition is closed) when RPM is over the 30 RPM (fix
value). Gas valve (binary output Gas is closed) is opened 1 sec after Ignition output.
Gas output opens after stop command or in pause between repeated start.
If the gas engine is unsuccessful in starting the starter output will stay energized 25% longer in order to vent
the remaining gas.
Fuel Solenoid