200 Series General Purpose Vector AC Drive Chapter 5 Functional Parameter Simple List
53
Adjust V1 to set the main frequency within the
range of F0-30
~
F0-31
FA-14
Line 2 normal
monitoring parameter
selection
The same as F9-01 selection
2
√
FA-15
Peed tracking DC
excitation
10
~
200%
130%
√
FA-16
Hardware tracking
excitation time
0
~
10.000s
0.100s
√
FA-17
Tracking frequency
calculation time
0
~
5.000s
0.200s
√
FA-18
Speed tracking voltage
soft start time
0.001
~
32.000s
0.500s
√
FA-19
Hardware tracking
direction
0:Present measurement direction
1:Add DC excitation and judge the direction
for each time
2: Memory running direction before stopping
3: Use the target frequency direction as the
tracking frequency direction
2
√
FA-20
Swing frequency setting
mode
0: Relative to center frequency
1: Relative to maximum frequency
0
√
FA-21
The start temperature of
the external fan startup
module during operation
5.0
~
50.0
℃
(The matching output terminal
function is set to 31, and it is forced to start
when the module temperature exceeds 50°C in
stop )
5.0
℃
√
FA-22 Random PWM depth
0
~
10
0
√
FA-23
Dead zone gain
adjustment
0
~
200
80
√
FA-24 Over modulation factor 90.0%
~
130.0%
110.0%
√
FA-28
Switch frequency point
between acceleration
time 1 and acceleration
time 2
0.00Hz
~
3000.0Hz
0.00Hz
√
*
FA-29
Switching frequency
point between
deceleration time 1 and
deceleration time 2
0.00Hz
~
3000.0Hz
0.00Hz
√
*
Group Fb: Protection Function Group
Fb-00
Protection function
selection 1
The unit: Over voltage at stall protect
0: Disabled 1: Enabled
Tens: Current limiting action selection
0: Valid 1: Invalid
1101 ×