200 Series General Purpose Vector AC Drive Chapter 5 Functional Parameter Simple List
49
(F7-08)
2: Faulty stop(E022)
Tens: Feedback over-voltage protect selection
0: Invalid
1: Alarm and operation in settled frequency
(F7-15)
2: Faulty stop(E024)
F7-02 Digit PID specified set
0.0
~
100.0%(100.0% Corresponding pressure
gauge range)
If the pressure gauge is 1.6MPA and the target
pressure is 0.2MPA (2kg), then F7-02 =
0.2MPA*100.0%/1.6MPA = 12.5%; if the
pressure gauge is 1.0MPA and the target
pressure is 0.2MPA (2kg), then F7-02 =
0.2MPA*100.0%/1.0MPA = 20.0%.
20.0%
√
F7-03 Proportional gain KP
0
~
32000( The larger the value, the faster the
response and the greater the oscillation)
4096
√
F7-04 Integral gain KI
0
~
32000(The larger the value, the faster the
response and the greater the overshoot
1500
√
F7-05
PID control deviation
limit
0.0
~
100.0%
The error between specified and feedback is
less than this setting, PID pause adjustment
0.0%
√
F7-06
PID feedback
disconnection detected
value
0.0
~
100.0%
Feedback disconnection detection: When the
feedback value is less than the feedback loss
detection value F7-06, the system starts the
detection timing. When the timing time exceeds
F7-07, the ac drive runs according to F7-01 in
priority.
0.0%
√
F7-07
Feedback disconnection
detected time
0.0
~
200.0s
2.0s
√
F7-08
Feedback disconnection
fixed output
0.0
~
100.0% Maximum frequency
50.0%
√
F7-09 Dormant
frequency
0.00Hz(no dormant)
~
Maximum
frequency(F0-05)
0.00Hz
√
F7-10 Dormant
delay
0.0
~
600.0s
when the running frequency is less than or
equal to the dormant frequency of F7-09 in ac
drive running, after the delay time of F7-10, the
drive enters the dormant state, stops
automatically, and the running indicator flashes.
10.0s
√
F7-11 Wakeup
deviation
0.0
~
100.0%
80.0%
√